Table 10.
All object types sorted by object name (continued)
Object Type
Object Name
Min / Max
When the Point Exists
Description
AV81
Outdoor Air Humidity
BAS
0 - 100%
All Units.
Communicated outdoor air
relative humidity.
AV71
Outdoor Air Minimum
Flow Setpoint
350 -
13500
cfm
Units that are VAV, have
Outdoor Air Flow
Monitoring, and
Modulating Dampers.
Setpoint to modulate the
dampers.
AV72
Outdoor Air Minimum
Flow Setpoint Active
350 -
13500
cfm
Units that are VAV, have
Outdoor Air Flow
Monitoring, and
Modulating Dampers.
Actively used setpoint to
modulate the dampers.
AV13
Outdoor Air Minimum
Flow Setpoint BAS
0 - 13500
cfm
VAV Units with Outdoor air
flow Monitoring and
Modulating Dampers.
air flow setpoint used to
modulate dampers.
AI22
Outdoor Air Relative
Humidity Local
0 - 100%
All Units.
Local outside air humidity
sensor.
AV76
Outdoor Air Temperature
Active
-100 to
200 °F
All Units.
Actively used outdoor air
temperature.
AV75
Outdoor Air Temperature
BAS
-100 to
200 °F
All Units.
Communicated outdoor air
temperature.
AI21
Outdoor Air Temperature
Local
-50 to 135
°F
All Units.
Local outside air temperature
sensor.
AO4
PEVFD Command
0 – 100%
Units with Powered
Exhaust.
Analog exhaust fan VFD speed.
AV40
PEVFD Setpoint
0 - 100%
OAD, OAK, or OAN that
does NOT have
Modulating Dampers or
Powered Exhaust.
Fan speed setpoint used to
control the indoor fan speed.
BO10
Powered Exhaust Enable
Units with Isolation
Dampers or has Dual Point
Power.
• 0 = Off
• 1 = On
BO13
Pre-Heat Enable
Units with Pre-Heat.
• 0 = Off
• 1 = On
AV58
Pre-Heat Enable
Temperature
-10 to 35 °F
Units with an ERV and an
Electric Pre-Heater.
Below this temperature pre-
heat will be enabled.
BV33
Pre-Purge Status
Units with Gas as the
Primary Heat.
• 0 = Disabled
• 1 = Enabled
MV13
Program Control Type
All Units.
• 1 = Space Control
• 2 = Discharge Control
• 3 = Single Zone VAV
• 4 = Multi Zone VAV
BV18
Return Air Damper
Option
All Units.
• 0 = Not Installed
• 1 = Installed
AI14
Return Air Humidity Local
0 - 100%
Units with Modulating
Dampers.
Local return air humidity
sensor.
AI6
Return Air Temperature
Local
-25 to 135
°F
Units with Modulating
Dampers.
Local return air temperature
sensor.
AI12
Return Duct/Space
Pressure Local
0 - 2 in(H
2
O)
Units with Powered
Exhaust and Modulating
Dampers.
Local return duct or space
pressure sensor
AV56
Return Duct/Space
Pressure Setpoint
0 - 2 in(H
2
O)
Units with Modulating
Dampers and Exhaust
Fan(s).
Setpoint used to modulate
exhaust fan speed.
AV50
Space CO2
Concentration Setpoint
0 – 3000
ppm
All Units.
Space CO2 concentration
setpoint.
AV35
Space Dewpoint Active
-58 to 482
°F
All Units.
Actively used space dewpoint.
AV34
Space Dewpoint Setpoint
(SPDS)
-10 – 150
°F
Units with Space Control,
Discharge Control, or
Single Zone VAV.
If the outdoor air dewpoint is
greater than OADS, the unit
will enable dehumidification.
AI16
Space Occupancy
Request Override
-58 to 482
Units with Thumbwheel
Installed.
Local input that overrides
Occupancy Request.
AI2
Space Relative Humidity
Local
0 – 100%
Units with Space Humidity
Sensor Installed
Local space relative humidity
sensor.
AV7
Space RH Active
-150 to
150%
Units with Space Humidity
Sensor Installed.
Actively used space relative
humidity.
AV8
Space RH BAS
-150 to
150%
All Units.
Communicated space relative
humidity.
BV20
Space Temp/Humidity
Sensor Installed
Units that are Space
Control or Single Zone
VAV.
• 0 = Not Installed
• 1 = Installed
AV23
Space Temperature
Active
-58 to 482
°F
All Units.
Actively used space
temperature.
AV20
Space Temperature BAS
-58 to 482
°F
All Units.
Communicated space
temperature.
AI1
Space Temperature Local
-25 to 135 °F
Units with Space
Temperature Sensor
Installed
Local space temperature
sensor.