Table 5. Analog values (continued)
Object Type
Object Name
Min / Max
When the Point Exists
Description
AV48
Minimum OA Damper
Position
0 – 100 %
Units with Modulating
Dampers.
Minimum outdoor air damper
position.
AV49
Duct Static Pressure
Setpoint
-1 to 6 in(H
2
O)
Units with Multi Zone VAV.
Setpoint used to modulate
indoor fan.
AV50
Space CO
2
Concentration Setpoints
0 – 3000 ppm
All Units.
Space CO
2
concentration
Setpoints
AV52
Cooling Capacity
0 – 100 %
Units with DX Cooling.
Primary cooling source
capacity.
AV53
Duct Static Pressure
Setpoint Active
-1 to 6 in(H
2
O)
Unit with Multizone VAV.
Actively used duct static
pressure setpoint.
AV54
Exhaust Air Flow Active
0 – 15000 cfm
Units with Piezo Ring on
the Exhaust Fan.
The amount of air delivered by
the exhaust fan.
AV56
Return Duct/Space
Pressure Setpoint
0 - 2 in(H
2
O)
Units with Modulating
Dampers and Exhaust Fan
(s).
Setpoint used to modulate
exhaust fan speed.
AV57
Exhaust Air Flow
Setpoint
0 – 7500 cfm
OAB or OAG units that are
208v or 460v, and does
not have Modulating
Dampers with Exhaust Fan
(s).
Setpoint used to modulate
exhaust fan speed.
AV58
Pre-Heat Enable
Temperature
-10 to 35 °F
Units with an ERV and an
Electric Pre-Heater.
Below this temperature pre-
heat will be enabled.
AV59
Minimum Supply Air
Flow Setpoint
300 – 13500 cfm
Units with Single Zone or
Multi Zone VAV.
Supply air flow is limited to not
fall below this number.
AV64
Duct Static Pressure BAS
-6 to 6 in(H
2
O)
Units with Multi Zone VAV.
Communicated duct static
pressure.
AV65
Duct Static Pressure
Active
-6 to 6 in(H
2
O)
Units with Multi Zone VAV.
Actively used duct static
pressure.
AV66
Discharge Air
Temperature Setpoint
Active
38 – 130 °F
Units with Multi Zone VAV.
Actively used discharge air
temperature setpoint.
AV67
Discharge Air
Temperature Setpoint
BAS
45 – 90 °F
Units with Multi Zone VAV.
Communicated discharge air
temperature setpoint.
AV68
Discharge Air
Temperature Setpoint
45 – 120 °F
Units with Multi Zone VAV.
Discharge air temperature
setpoint.
AV69
Heat/Cool Mode
Deadband
-58 to 482 °F
Units with Multi Zone VAV.
Heat is enabled when Outdoor
Air Temperature drops below
Discharge Temperature
Setpoint
- Heat/Cool Mode Deadband.
Cooling is enabled when
Outdoor Air temperature rises
above the Discharge
Temperature Setpoint.
AV70
Maximum Supply Air
Flow Setpoint
350 – 13500 cfm
Units with Single Zone or
Multi Zone VAV.
Supply air flow is limited to not
exceed this number.
AV71
Outdoor Air Minimum
Flow Setpoint
350 – 13500 cfm
Units that are VAV, have
Outdoor Air Flow
Monitoring, and
Modulating Dampers.
Setpoint to modulate the
dampers.
AV72
Outdoor Air Minimum
Flow Setpoint Active
350 – 13500 cfm
Units that are VAV, have
Outdoor Air Flow
Monitoring, and
Modulating Dampers.
Actively used setpoint to
modulate the dampers.
AV75
Outdoor Air Temperature
BAS
-100 to 200 °F
All Units.
Communicated outdoor air
temperature.
AV76
Outdoor Air Temperature
Active
-100 to 200 °F
All Units.
Actively used outdoor air
temperature.
AV81
Outdoor Air Humidity
BAS
0 - 100%
All Units.
Communicated outdoor air
relative humidity.
AV82
Outdoor Air Humidity
Active
0 - 100%
All Units.
Actively used outdoor air
relative humidity.