30
BAS-SVP18D-EN
Table 10.
All object types sorted by object name (continued)
Object Type
Object Name
Min / Max
When the Point Exists
Description
AV45
Maximum Supply Air
Temperature
80 – 120
°F
All Units with Primary
Heat or Heat Pumps
Primary or Compressor
Heating Capacity is limited in
order to not exceed this
temperature.
AV36
Minimum Discharge Air
Cooling Setpoint
40 – 65 °F
Units that are Space
Control.
Cooling capacity is limited in
order to not fall below this
temperature.
AV43
Minimum Discharge Air
Heating Setpoint
40 – 65 °F
Units that are Space
Control.
Primary or Compressor
Heating
Capacity is limited in order to
not fall below this
temperature.
AV48
Minimum OA Damper
Position
0 - 100%
Units with Modulating
Dampers.
Minimum outdoor air damper
position.
AV59
Minimum Supply Air Flow
Setpoint
300 –
13500 cfm
Units with Single Zone or
Multi Zone VAV.
Supply air flow is limited to not
fall below this number.
BI5
OA Damper End Switch
All Units.
Normally open input.
• 0 = Not Proven
• 1 = Proven
AO5
OAD Position Command
0 - 100%
Units with Modulating
Dampers.
Analog outdoor air damper
command.
AI7
OAD Position Local
0 - 100%
Units with Modulating
Dampers.
Local outside air damper
position.
BI4
Occupancy Input
All Units.
Normally open input.
• 0 = Unoccupied
• 1 = Occupied
MV1
Occupancy Request
All Units.
• 1 = Occupied
• 2 = Unoccupied
• 3 = Occupied Bypass
• 4 = Occupied Standby
• 5 = Auto
MV2
Occupancy Status
All Units.
• 1 = Occupied
• 2 = Unoccupied
• 3 = Occupied Bypass
• 4 = Occupied Standby
• 5 = Unknown
AV9
Occupied Bypass Time
2 - 360
Units with Thumbwheel
Installed.
Time that Unoccupied Mode is
delayed when Occupied Button
is pressed.
AV1
Occupied Cooling
Setpoint
55 – 85 °F
Units with Space Control
or Single Zone VAV.
Space cooling setpoint used in
occupied mode.
AV2
Occupied Heating
Setpoint
55 – 85 °F
Units with Space Control
or Single Zone VAV.
Space heating setpoint used in
occupied mode.
AV3
Occupied Offset
0.5 – 30 Δ
°F
All Units.
The value used to calculate the
heating/cooling setpoints in
occupied mode. If the unit has
a thumbwheel installed
Occupied Offset defaults to 2.
Active heating setpoint =
active setpoint – occupied
offset.
Active cooling setpoint =
active se occupied
offset.
AV29
Outdoor Air Cooling
Setpoint (OACS)
60 – 90 °F
Units with Space Control,
Discharge Control, or
Single Zone
VAV.
Setpoint used to enable
cooling.
BO2
Outdoor Air Damper
Command
All Units.
• 0 = Open
• 1 = Closed
AV11
Outdoor Air Dewpoint
Active
-10 to 150
°F
All Units.
Dewpoint of the outdoor air.
This point is calculated within
the program.
AV10
Outdoor Air Dewpoint
Setpoint (OADS)
49 – 100
°F
Units with Space Control,
Discharge Control, or
Single Zone VAV.
If the outdoor air dewpoint is
greater than OADS, the unit
will enable dehumidification.
AV38
Outdoor Air Flow Active
0 - 13500
cfm
Units with Outside Air
Flow Monitoring.
Actively used outside air flow.
AI10
Outdoor Air Flow Local
0 - 15000
cfm
Units with Outside air flow
Monitoring.
Local outside air flow.
AV33
Outdoor Air Heating
Setpoint (OAHS)
40 – 75 °F
Units with Space Control,
Discharge Control, or
Single Zone VAV.
Setpoint used to enable
heating.
AV82
Outdoor Air Humidity
Active
0 – 100%
All Units.
Actively used outdoor air
relative humidity.