BAS-SVP18D-EN
29
Table 10.
All object types sorted by object name (continued)
Object Type
Object Name
Min / Max
When the Point Exists
Description
BO9
Exhaust Damper
Actuators
Units with Isolation
Dampers.
• 0 = Off
• 1 = On
BI7
Exhaust Damper
Endswitch
Units with Isolation
Dampers.
Normally open input.
• 0 = Not Proven
• 1 = Proven
AI9
Exhaust Fan Pressure
Local
0 - 25 in(H
2
O)
Units with Piezo Ring on
Exhaust Fan.
Local exhaust fan piezo ring
pressure.
AI13
Exhaust Leaving
Temperature Local
-25 to 135
°F
Units with an ERV.
Local exhaust leaving
temperature sensor
BI3
Filter Status
All Units.
Normally open input.
• 0 = Clean
• 1 = Clogged
BI6
Gas Valve Status
Units with Gas as the
Primary Heat.
Normally open input.
• 0 = Off
• 1 = On
BO3
Heat 1 Command
Units with Primary Heat.
• 0 = Off
• 1 = On
BO7
Heat 2 Command
Units with Gas as the
Primary Heat and is a Split
Manifold Burner.
• 0 = Off
• 1 = On
BO8
Heat 3 Command
Units with Gas as the
Primary Heat and has Two
Heaters.
• 0 = Off
• 1 = On
AV44
Heat Capacity
0 – 100%
Units with Primary Heat.
Primary heating source
capacity.
BV21
Heat Cool Mode Active
All Units.
• 0 = Heat
• 1 = Cool
MV4
Heat Cool Mode Status
All Units
• 1 = Auto
• 2 = Heat
• 3 = Morning Warm-up
• 4 = Cool
• 5 = Night Purge
• 6 = Pre Cool
• 7 = Off
MV9
Heat Type
All Units
• 1 = No Heat
• 2 = Indirect Fired Gas Heat
• 3 = Electric Heat
• 4 = Other
• 5 = Direct Fired Gas Heat
• 6 = Hot Water/Steam
AV69
Heat/Cool Mode
Deadband
-58 to 482
°F
Units with Multi Zone VAV.
Heat is enabled when Outdoor
Air Temperature drops below
Discharge Temperature
Setpoint - Heat/Cool Mode
Deadband. Cooling is enabled
when Outdoor Air temperature
rises above the Discharge
Temperature Setpoint.
AO11
Heating Output
Command
0 – 100%
Units with any type of
Primary Heat.
Analog heating output
command.
AO1
HGRH Command
0 - 100%
Units with Modulating Hot
Gas Reheat.
Analog HGRH output
command.
BV5
HGRH Purge Mode
Units with Hot Gas
Reheat.
• 0 = Disabled
• 1 = Enabled
BV15
High Temp Lockout
All Units.
Latching diagnostic. Cleared
with Alarm Reset.
• 0 = Normal
• 1 = Fail
BO4
Inducer Command
Units with Gas as the
Primary Heat.
• 0 = Off
• 1 = On
AO2
IVFD Command
0 - 100%
All Units.
Analog supply fan VFD speed.
AV17
IVFD Signal
50 - 100%
When Unit is an OAD,
OAK, or OAN and the
Supply Fan is CV.
Supply fan speed setpoint.
AV12
Liquid Line Pressure
Setpoint
200 – 600
psi
Air Source Heat Pumps
with Head Pressure
Control.
Pressure setpoint used to
modulate condenser fan(s).
BV10
Low Temp Lockout
All Units.
Latching diagnostic. Cleared
with Alarm Reset.
• 0 = Normal
• 1 = Fail
AV47
Maximum OA Damper
Position
0 - 100%
Units with Modulating
Dampers.
Maximum outdoor air damper
position.
AV70
Maximum Supply Air
Flow Setpoint
350 –
13500 cfm
Units with Single Zone or
Multi Zone VAV.
Supply air flow is limited to not
exceed this number.