16
BAS-SVP18D-EN
Table 2. Descriptions and configurations (continued)
Object Type
Required Properties
Read
Properties Written
Optional Properties
Read
Ability to
Create
Ability to Delete
Binary Value
• Object_Identifier
• Object_Name
• Object_Type
• Present_Value
• Status_Flags
• Event_State
• Out_Of_Service
• Polarity
• Object_Name
• Description
• Out_Of_Service
• Inactive_Text
• Active_Text
• Present_Value
• Reliability
• Change_Of_State_
Count
• Elapsed_Active_Time
• Minimum_On_Time
• Minimum_Off_Time
• Relinquish_Default
• Time_Delay
• Notification_Class
• Event_Enable
• Acked_Transitions
• Notify_Type
• Description
• Inactive_Text
• Active_Text
• Change_Of_State_Time
• Change_Of_State_Count
• Time_Of_State_Count_
Reset
• Elapsed_Active_Time
• Time_Of_Active_Time_
Reset
• Priority_Array
• Relinquish_Default
• Minimum_On_Time
• Minimum_Off_Time
• Time_Delay
• Notification_Class
• Alarm_Value
• Event_Enable
• Acked_Transitions
• Notify_Type
• Event_Time_Stamps
• Reliability
Yes
Yes, user create
objects only
Device
• Object_Identifier
• Object_Name
• Object_Type
• System_Status
• Vendor_Name
• Vendor_Identifier
• Model_Name
• Firmware_Revision
• Application_Software_
Version
• Protocol_Version
• Protocol_Revision
• Protocol_Services_
Supported
• Protocol_Object_Types_
Supported
• Object_List
• Max_APDU_Length_
Accepted
• Segmentation_
Supported
• APDU_Timeout
• Number_Of_APDU_
Retries
• Device_Address_Binding
• Database_Revision
• Object_Name
• Location
• Description
• APDU_Segment_
Timeout
• APDU_Timeout
• Number_Of_APDU_
Retries
• Backup_Failure_Timeout
• Max_Master
• Max_Info_Frames
• Location
• Description
• Max_Segments_
Accepted
• APDU_Segment_
Timeout
• Max_Master
• Max_Info_Frames
• Local_Time
• Local_Date
• Configuration_Files
• Last_Restore_Time
• Backup_Failure_Timeout
• Profile_Name
None
None
Event
Enrollment
Object
• Object_Identifier
• Object_Name
• Object_Type
• Event_Type
• Notify_Type
• Event_Parameters
• Object_Property_
Reference
• Event_State
• Event_Enable
• Acked_Transitions
• Notification_Class
• Event_Time_Stamps
• Object_Name
• Notify_Type
• Event_Parameters
• Object_Property_
Reference
• Event_Enable
• Notification_Class
• None
Yes
Yes, user create