28
BAS-SVP18D-EN
Table 10.
All object types sorted by object name (continued)
Object Type
Object Name
Min / Max
When the Point Exists
Description
BV13
Diagnostic: Outdoor Air
Temperature Source
Failure
All Units.
Auto-Reset diagnostic.
• 0 = Normal
• 1 = Fail
BV12
Diagnostic: Space
Humidity Source Failure
Units that are Space
Control or Single Zone
VAV.
Auto-Reset diagnostic.
• 0 = Normal
• 1 = Fail
BV19
Diagnostic: Space RH
Source Failure
Units that are Space
Control or Single Zone
VAV.
Auto-Reset diagnostic.
• 0 = Normal
• 1 = Fail
BV2
Diagnostic: Space
Temperature Setpoint
Failure
Units with Thumbwheel
Installed.
• 0 = Normal
• 1 = Fail
BV11
Diagnostic: Space
Temperature Source
Failure
Units that are Space
Control or Single Zone
VAV.
Auto-Reset diagnostic.
• 0 = Normal
• 1 = Fail
BV1
Diagnostic: Supply Fan
Failure
All Units.
Latching diagnostic. Cleared
with Alarm Reset.
• 0 = Normal
• 1 = Fail
AV30
Discharge Air Cooling
Setpoint
47 – 90 °F
Units with Discharge Air
Control.
Discharge air setpoing during
cooling mode.
AV32
Discharge Air Heating
Setpoint
45 – 100 °F
Units with Discharge Air
Control.
Discharge air setpoing during
heating mode.
AV5
Discharge Air
Temperature Active
-10 to 150
°F
All Units.
Actively used discharge air
temperature.
AV4
Discharge Air
Temperature BAS
-10 to 150
°F
All Units.
Communicated discharge air
temperature.
AI11
Discharge Air
Temperature Local
-25 to 135
°F
All Units.
Local discharge air
temperature sensor.
AV68
Discharge Air
Temperature Setpoint
45 – 120 °F
Units with Multi Zone VAV.
Discharge air temperature
setpoint.
AV66
Discharge Air
Temperature Setpoint
Active
38 -130 °F
Units with Multi Zone VAV.
Actively used discharge air
temperature setpoint.
AV67
Discharge Air
Temperature Setpoint
BAS
45 – 90 °F
Units with Multi Zone VAV.
Communicated discharge air
temperature setpoint.
AV65
Duct Static Pressure
Active
-6 to 6 in(H
2
O)
Units with Multi Zone VAV.
Actively used duct static
pressure.
AV64
Duct Static Pressure BAS
-6 to 6 in(H
2
O)
Units with Multi Zone VAV.
Communicated duct static
pressure.
AI23
Duct Static Pressure
Local
0 - 2 in(H
2
O)
Unit with Multizone VAV.
Local supply duct pressure
sensor.
AV49
Duct Static Pressure
Setpoint
-1 to 6 in(H
2
O)
Units with Multi Zone VAV.
Setpoint used to modulate
indoor fan.
AV53
Duct Static Pressure
Setpoint Active
-1 to 6 in(H
2
O)
Unit with Multizone VAV.
Actively used duct static
pressure setpoint.
AV46
Duct Static Pressure
Setpoint BAS
-1 to 6 in(H
2
O)
Unit with Multizone VAV.
Communicated duct static
pressure setpoint.
BV45
Economizer Control Type
All Units.
• 0 = Dry Bulb
• 1 = Dry Bulb and Enthalpy
BV9
Economizer Mode
Units with Modulating
Dampers.
• 0 = Disabled
• 1 = Enabled
AO6
ERV Bypass Position
Command
0 - 100%
Units with ERV.
Analog ERV bypass damper
command.
BO15
ERV Command
Units with an ERV.
• 0 = Off
• 1 = On
AI17
ERV Supply Side Leaving
Temperature Local
-58 to 482
°F
Units with an ERV and is a
Water Source Heat Pump.
Local temperature sensor
located post ERV on the supply
air side.
BI2
ESTOP
All Units.
Normally Open Input. Auto-
Reset diagnostic.
• 0 = Normal
• 1 = ESTOP
AI15
Evaporator Coil Leaving
Temperature Local
-25 to 135
°F
Units with Compressors.
Local evaporator leaving air
temperature sensor.
AV14
Evaporator Leaving
Temperature Setpoint
45 – 75 °F
All Units.
Evaporator leaving air
temperature setpoint during
dehumidification mode or
Single Zone VAV
AV54
Exhaust Air Flow Active
0 – 15000
cfm
Units with Piezo Ring on
the Exhaust Fan.
The amount of air delivered by
the exhaust fan.
AV57
Exhaust Air Flow
Setpoint
0 – 7500
cfm
OAB or OAG units that are
208v or 460v, and does
not have Modulating
Dampers with Exhaust
Fan(s).
Setpoint used to modulate
exhaust fan speed.