BAS-SVP18D-EN
21
Table 5. Analog values (continued)
Object Type
Object Name
Min / Max
When the Point Exists
Description
AV16
DAT Temp Cutout Time
10 - 25
All Units.
Time required for low limit or
high limit temperature to
signal alarm.
AV17
IVFD Signal
50 - 100%
When Unit is an OAD, OAK,
or OAN and the Supply Fan
is CV.
Supply fan speed setpoint.
AV18
Compressor Heating
Capacity
0 – 100%
Units that are Air Source
or Water Source Heat
Pumps.
Compressor Heating source
capacity.
AV20
Space Temperature BAS
-58 to 482 °F
All Units.
Communicated space
temperature.
AV23
Space Temperature
Active
-58 to 482 °F
All Units.
Actively used space
temperature.
AV24
Condenser Coil
Temperature Setpoint
80 to 125 °F
Units with Head Pressure
Control and isn't an Air
Source Heat Pump.
Temperature setpoint used to
modulate condenser fan(s).
AV25
Space Temperature
Setpoint BAS
-58 to 482 °F
Units that are Space
Control or Single Zone
VAV.
Communicated space
temperature setpoint.
AV26
Unoccupied Cooling
Setpoint
60 to 90 °F
Units with Space
Temperature/Humidity
Sensor Installed.
Space cooling setpoint used in
unoccupied mode.
AV27
Unoccupied Heating
Setpoint
45 to 90 °F
Units with Space
Temperature/Humidity
Sensor Installed.
Space heating setpoint used in
unoccupied mode.
AV28
Unoccupied Dewpoint
Setpoint
49 to 100 °F
Units with Space
Temperature/Humidity
Sensor Installed.
If the space dewpoint rises
above this setpoint during
unoccupied mode then
dehumidification will be
enabled.
AV29
Outdoor Air Cooling
Setpoint (OACS)
60 – 90 °F
Units with Space Control,
Discharge Control, or
Single Zone VAV.
Setpoint used to enable
cooling.
AV30
Discharge Air Cooling
Setpoint
47 – 90 °F
Units with Discharge Air
Control.
Discharge air setpoint during
cooling mode.
AV31
Compressor Count
0 - 4
Units with DX Cooling.
Number of compressors
installed in the unit.
AV32
Discharge Air Heating
Setpoint
45 – 100 °F
Units with Discharge Air
Control.
Discharge air setpoing during
heating mode.
AV33
Outdoor Air Heating
Setpoint (OAHS)
40 – 75 °F
Units with Space Control,
Discharge Control, or
Single Zone VAV.
Setpoint used to enable
heating.
AV34
Space Dewpoint
Setpoint (SPDS)
-10 – 150 °F
Units with Space Control,
Discharge Control, or
Single Zone VAV.
If the outdoor air dewpoint is
greater than OADS, the unit
will enable dehumidification.
AV35
Space Dewpoint Active
-58 to 482 °F
All Units.
Actively used space dewpoint.
AV36
Minimum Discharge Air
Cooling Setpoint
40 – 65 °F
Units that are Space
Control.
Cooling capacity is limited in
order to not fall below this
temperature.
AV37
Space Temperature
Setpoint Active
45 – 95 °F
Units that are Space
Control or Single Zone
VAV.
Actively used space
temperature setpoint.
AV38
Outdoor Air Flow Active
0 – 13500 cfm
Units with Outside Air Flow
Monitoring.
Actively used outside air flow.
AV39
Supply Air Flow Setpoint
0 – 7500 cfm
OAB or OAG units that are
208v or 460v.
Setpoint used to modulate the
indoor fan speed.
AV40
PEVFD Setpoint
0 – 100 %
OAD, OAK, or OAN that
does NOT have Modulating
Dampers or Powered
Exhaust.
Fan speed setpoint used to
control the indoor fan speed.
AV41
Supply Air Flow Active
0 – 15000 cfm
Units with Piezo Ring on
Supply Fan.
Actively used supply airflow.
AV43
Minimum Discharge Air
Heating Setpoint
40 - 65 °F
Units that are Space
Control.
Primary or Compressor
Heating Capacity is limited in
order to not fall below this
temperature.
AV44
Heat Capacity
0 – 100 %
Units with Primary Heat.
Primary heating source
capacity.
AV45
Maximum Supply Air
Temperature
80 – 120 °F
All Units with Primary Heat
or Heat Pumps
Primary or Compressor
Heating Capacity is limited in
order to not exceed this
temperature.
AV46
Duct Static Pressure
Setpoint BAS
-1 to 6 in(H
2
O)
Unit with Multizone VAV.
Communicated duct static
pressure setpoint.
AV47
Maximum OA Damper
Position
0 – 100 %
Units with Modulating
Dampers.
Maximum outdoor air damper
position.