BAS-SVP18D-EN

21

Table 5. Analog values (continued)

Object Type

Object Name

Min / Max

When the Point Exists

Description

AV16

DAT Temp Cutout Time

10 - 25

All Units.

Time required for low limit or
high limit temperature to
signal alarm.

AV17

IVFD Signal

50 - 100%

When Unit is an OAD, OAK,
or OAN and the Supply Fan
is CV.

Supply fan speed setpoint.

AV18

Compressor Heating
Capacity

0 – 100%

Units that are Air Source
or Water Source Heat
Pumps.

Compressor Heating source
capacity.

AV20

Space Temperature BAS

-58 to 482 °F

All Units.

Communicated space
temperature.

AV23

Space Temperature
Active

-58 to 482 °F

All Units.

Actively used space
temperature.

AV24

Condenser Coil
Temperature Setpoint

80 to 125 °F

Units with Head Pressure
Control and isn't an Air
Source Heat Pump.

Temperature setpoint used to
modulate condenser fan(s).

AV25

Space Temperature
Setpoint BAS

-58 to 482 °F

Units that are Space
Control or Single Zone
VAV.

Communicated space
temperature setpoint.

AV26

Unoccupied Cooling
Setpoint

60 to 90 °F

Units with Space
Temperature/Humidity
Sensor Installed.

Space cooling setpoint used in
unoccupied mode.

AV27

Unoccupied Heating
Setpoint

45 to 90 °F

Units with Space
Temperature/Humidity
Sensor Installed.

Space heating setpoint used in
unoccupied mode.

AV28

Unoccupied Dewpoint
Setpoint

49 to 100 °F

Units with Space
Temperature/Humidity
Sensor Installed.

If the space dewpoint rises
above this setpoint during
unoccupied mode then
dehumidification will be
enabled.

AV29

Outdoor Air Cooling
Setpoint (OACS)

60 – 90 °F

Units with Space Control,
Discharge Control, or
Single Zone VAV.

Setpoint used to enable
cooling.

AV30

Discharge Air Cooling
Setpoint

47 – 90 °F

Units with Discharge Air
Control.

Discharge air setpoint during
cooling mode.

AV31

Compressor Count

0 - 4

Units with DX Cooling.

Number of compressors
installed in the unit.

AV32

Discharge Air Heating
Setpoint

45 – 100 °F

Units with Discharge Air
Control.

Discharge air setpoing during
heating mode.

AV33

Outdoor Air Heating
Setpoint (OAHS)

40 – 75 °F

Units with Space Control,
Discharge Control, or
Single Zone VAV.

Setpoint used to enable
heating.

AV34

Space Dewpoint
Setpoint (SPDS)

-10 – 150 °F

Units with Space Control,
Discharge Control, or
Single Zone VAV.

If the outdoor air dewpoint is
greater than OADS, the unit
will enable dehumidification.

AV35

Space Dewpoint Active

-58 to 482 °F

All Units.

Actively used space dewpoint.

AV36

Minimum Discharge Air
Cooling Setpoint

40 – 65 °F

Units that are Space
Control.

Cooling capacity is limited in
order to not fall below this
temperature.

AV37

Space Temperature
Setpoint Active

45 – 95 °F

Units that are Space
Control or Single Zone
VAV.

Actively used space
temperature setpoint.

AV38

Outdoor Air Flow Active

0 – 13500 cfm

Units with Outside Air Flow
Monitoring.

Actively used outside air flow.

AV39

Supply Air Flow Setpoint

0 – 7500 cfm

OAB or OAG units that are
208v or 460v.

Setpoint used to modulate the
indoor fan speed.

AV40

PEVFD Setpoint

0 – 100 %

OAD, OAK, or OAN that
does NOT have Modulating
Dampers or Powered
Exhaust.

Fan speed setpoint used to
control the indoor fan speed.

AV41

Supply Air Flow Active

0 – 15000 cfm

Units with Piezo Ring on
Supply Fan.

Actively used supply airflow.

AV43

Minimum Discharge Air
Heating Setpoint

40 - 65 °F

Units that are Space
Control.

Primary or Compressor
Heating Capacity is limited in
order to not fall below this
temperature.

AV44

Heat Capacity

0 – 100 %

Units with Primary Heat.

Primary heating source
capacity.

AV45

Maximum Supply Air
Temperature

80 – 120 °F

All Units with Primary Heat
or Heat Pumps

Primary or Compressor
Heating Capacity is limited in
order to not exceed this
temperature.

AV46

Duct Static Pressure
Setpoint BAS

-1 to 6 in(H

2

O)

Unit with Multizone VAV.

Communicated duct static
pressure setpoint.

AV47

Maximum OA Damper
Position

0 – 100 %

Units with Modulating
Dampers.

Maximum outdoor air damper
position.

O

Ob

bjje

ecctt a

an

nd

d D

Diia

ag

gn

no

ossttiicc D

Da

atta

a P

Po

oiin

nttss

Содержание Tracer UC600

Страница 1: ...uires specific knowledge and training Improperly installed adjusted or altered equipment by an unqualified person could result in death or serious injury When working on the equipment observe all prec...

Страница 2: ...ctices are important to the environment our customers and the air conditioning industry All technicians who handle refrigerants must be certified according to local rules For the USA the Federal Clean...

Страница 3: ...o of f e en ne er rg gi iz ze ed d e el le ec ct tr ri ic ca al l c co on nt ta ac ct t a ar rc c o or r f fl la as sh h t te ec ch hn ni ic ci ia an ns s M MU US ST T p pu ut t o on n a al ll l P PP...

Страница 4: ...0 3rd Party BAS Integration 10 Tracer SC BAS Integration 11 BAS Unit Control 11 Initiating System Control 12 Routinely Updating BAS Values 12 Alarm Reset 12 BACnet Data Points and Configuration Proper...

Страница 5: ...utomation and Control Network BACnet protocol is ANSI ASHRAE Standard 135 This standard allows building automation systems or components from different manufacturers to share information and control f...

Страница 6: ...RX TX UC600 ADDRESS 0 1 2 3 4 5 6 7 8 9 x1 0 1 2 3 4 5 6 7 8 9 x10 0 1 2 3 4 5 6 7 8 9 x100 BO4 BO3 BO2 BO1 ADDRESS 0 1 2 3 4 5 6 7 8 9 x1 0 1 2 3 4 5 6 7 8 9 x10 0 1 2 3 4 5 6 7 8 9 x100 Rotary switc...

Страница 7: ...on solid yellow Reverse polarity is present LED not illuminated The controller is not detecting communication Cycle the power to re establish communication Verify that the controller is capable of com...

Страница 8: ...8 BAS SVP18D EN U UC C6 60 00 0 R Ro ot ta ar ry y S Sw wi it tc ch he es s a an nd d L LE ED Ds s...

Страница 9: ...on USB cable radio button if it is not already selected 4 Click the Connect button and the Unit Summary page displays after successful connection Configuration At the Unit Summary page 1 Enter a meani...

Страница 10: ...e ID box and enter a BACnet Device ID 8 Click Save 9 Cycle power to the device to have the new value take effect MS TP MAC Address Each device on a BACnet MS TP network must be assigned a unique physi...

Страница 11: ...e the new value take effect N No ot te e When the software method is enabled the hardware method is automatically disabled Figure 3 Example showing rotary dial settings and the BACnet device ID Tracer...

Страница 12: ...itions This may result in decreased occupant comfort and damage to building systems Alarm Reset The UC600 control system monitors the operation of the HVAC equipment If an abnormal condition is detect...

Страница 13: ...TP communications interface for Trane IntelliPak ReliaTel and CH530 controls Standardized Device Profile Annex L Profile Description Supported Profile BACnet Advanced Application Controller B AAC BAC...

Страница 14: ...t_State Out_Of_Service Units Object_Name Description Out_Of_Service Present_Value Reliability Min_Pres_Value Max_Pres_Value COV_Increment Time_Delay Notification_Class High_Limit Low_Limit Deadband Li...

Страница 15: ...able Polarity Notify_Type Description Inactive_Text Active_Text Change_Of_State_Time Change_Of_State_Count Time_Of_State_Count_ Reset Elapsed_Active_Time Time_Of_Active_Time_ Reset Time_Delay Notifica...

Страница 16: ..._Status Vendor_Name Vendor_Identifier Model_Name Firmware_Revision Application_Software_ Version Protocol_Version Protocol_Revision Protocol_Services_ Supported Protocol_Object_Types_ Supported Object...

Страница 17: ...Object_Type Present_Value Status_Flags Event_State Out_Of_Service Number_Of_States Object_Name Description State_Text Out_Of_Service Present_Value Reliability Priority_Array Relinquish_Default Time_De...

Страница 18: ...e 10 Baud Rate s 9600 19200 38400 Device Address Binding Device Address Binding Supported Static Device Binding Supported Networking Options Networking Descriptions Supported Option Annex H BACnet Tun...

Страница 19: ...flow Monitoring Local outside air flow AI11 Discharge Air Temperature Local 25 to 135 F All Units Local discharge air temperature sensor AI12 Return Duct Space Pressure Local 0 2 in H2O Units with Pow...

Страница 20: ...4 Discharge Air Temperature BAS 10 to 150 F All Units Communicated discharge air temperature AV5 Discharge Air Temperature Active 10 to 150 F All Units Actively used discharge air temperature AV6 DAT...

Страница 21: ...100 F Units with Discharge Air Control Discharge air setpoing during heating mode AV33 Outdoor Air Heating Setpoint OAHS 40 75 F Units with Space Control Discharge Control or Single Zone VAV Setpoint...

Страница 22: ...tic Pressure Active 6 to 6 in H2O Units with Multi Zone VAV Actively used duct static pressure AV66 Discharge Air Temperature Setpoint Active 38 130 F Units with Multi Zone VAV Actively used discharge...

Страница 23: ...BO2 Outdoor Air Damper Command All Units 0 Open 1 Closed BO3 Heat 1 Command Units with Primary Heat 0 Off 1 On BO4 Inducer Command Units with Gas as the Primary Heat 0 Off 1 On BO5 Compressor 3 Comman...

Страница 24: ...gnostic Space Humidity Source Failure Units that are Space Control or Single Zone VAV Auto Reset diagnostic 0 Normal 1 Fail BV13 Diagnostic Outdoor Air Temperature Source Failure All Units Auto Reset...

Страница 25: ...ic Pressure Failure Units that are Multi Zone VAV Auto Reset diagnostic 0 Normal 1 Fail BV37 Unoccupied Dehumid Mode BAS All Units 0 Disabled 1 Enabled BV38 Unoccupied Heating Mode BAS All Units 0 Dis...

Страница 26: ...nalog digital scroll or variable speed output command AI18 Circuit 1 Liquid Line Pressure Local 0 500 psi Units with Head Pressure Control and is an Air Source Heat Pump Local refrigerant pressure sen...

Страница 27: ...erature is greater than the discharge air high limit for AV16 minutes the controller signals an alarm and shuts down the unit AV15 DAT Low Temp Cutout 35 50 F All Units If the discharge air temperatur...

Страница 28: ...e air temperature setpoint AV65 Duct Static Pressure Active 6 to 6 in H2O Units with Multi Zone VAV Actively used duct static pressure AV64 Duct Static Pressure BAS 6 to 6 in H2O Units with Multi Zone...

Страница 29: ...Gas Heat 6 Hot Water Steam AV69 Heat Cool Mode Deadband 58 to 482 F Units with Multi Zone VAV Heat is enabled when Outdoor Air Temperature drops below Discharge Temperature Setpoint Heat Cool Mode Dea...

Страница 30: ...l Installed Time that Unoccupied Mode is delayed when Occupied Button is pressed AV1 Occupied Cooling Setpoint 55 85 F Units with Space Control or Single Zone VAV Space cooling setpoint used in occupi...

Страница 31: ...All Units 1 Space Control 2 Discharge Control 3 Single Zone VAV 4 Multi Zone VAV BV18 Return Air Damper Option All Units 0 Not Installed 1 Installed AI14 Return Air Humidity Local 0 100 Units with Mod...

Страница 32: ...0 Disabled 1 Enabled BV22 Unoccupied Cooling Mode BAS All Units 0 Disabled 1 Enabled AV26 Unoccupied Cooling Setpoint 60 90 F Units with Space Temperature Humidity Sensor Installed Space cooling setpo...

Страница 33: ...red with Alarm Reset or power cycle 2 BV11 Diagnostic Space Temperature Source Failure 0 Normal 1 Fail Latching diagnostic Cleared with Alarm Reset or power cycle 2 BV12 Diagnostic Space Humidity Sour...

Страница 34: ...pplication Guide BAS APG008 Tracer TU Online Help Tracer TU Service Tool Getting Started Guide TTU SVN01 Tracer UC600 Installation Instructions X39641178 01 Tracer XM30 Expansion Module Installation I...

Страница 35: ...BAS SVP18D EN 35 N No ot te es s...

Страница 36: ...For more information please visit trane com or tranetechnologies com Trane has a policy of continuous product and product data improvements and reserves the right to change design and specifications w...

Отзывы: