Table 8. Binary values (continued)
Object Type
Object Name
Min /Max
When the Point
Exists
Description
BV25
Compressor Stage 1
Request
None/None
Units with 1+
Compressors.
• 0 = Off
• 1 = On
BV26
Cooling Lockout BAS
Units with DX Cooling.
• 0 = Normal
• 1 = Lockout
BV27
Dehumidification
Command
Units that are Space
Control, Single Zone
VAV, or Discharge
Control.
• 0 = Disabled
• 1 = Enabled
BV28
Thumbwheel Installed
All Units.
• 0 = Not Installed
• 1 = Installed
BV29
Compressor Stage 2
Request
Units with 2+
Compressors.
• 0 = Off
• 1 = On
BV30
Compressor Stage 3
Request
Units with 3+
Compressors.
• 0 = Off
• 1 = On
BV31
Compressor Stage 4
Request
Units with 4
Compressors.
• 0 = Off
• 1 = On
BV32
Diagnostic: ERV Leaving
Air Conditions Failure
Units that are Water
Source Heat Pump with
an ERV.
Auto-Reset diagnostic.
• 0 = Normal
• 1 = Fail
BV33
Pre-Purge Status
Units with Gas as the
Primary Heat.
• 0 = Disabled
• 1 = Enabled
BV34
Diagnostic: Evap Temp
Source Failure
Units with DX Cooling.
Auto-Reset diagnostic.
• 0 = Normal
• 1 = Fail
BV35
Y1 Space Lockout
Units that are Space
Control or Single
Zone VAV.
• 0 = Disabled
• 1 = Enabled
BV36
Diagnostic: Duct Static
Pressure Failure
Units that are Multi Zone
VAV.
Auto-Reset diagnostic.
• 0 = Normal
• 1 = Fail
BV37
Unoccupied Dehumid
Mode BAS
All Units.
• 0 = Disabled
• 1 = Enabled
BV38
Unoccupied Heating Mode
BAS
All Units.
• 0 = Disabled
• 1 = Enabled
BV39
Unoccupied Heating Mode
All Units.
• 0 = Disabled
• 1 = Enabled
BV40
Unoccupied Dehumid
Mode
All Units.
• 0 = Disabled
• 1 = Enabled
BV42
Diagnostic: Heat Failure
Units with Gas as the
Primary Heat.
Auto-Reset diagnostic.
• 0 = Normal
• 1 = Fail
BV43
Ventilation
Units that are Space
Control, Single Zone VAV,
or Discharge Control.
• 0 = Disabled
• 1 = Enabled
BV45
Economizer Control Type
All Units.
• 0 = Dry Bulb
• 1 = Dry Bulb and Enthalpy
Table 9. Multi-state values
Object Type
Object Name
Min / Max
When the Point
Exists
Description
MV1
Occupancy Request
All Units.
• 1 = Occupied
• 2 = Unoccupied
• 3 = Occupied Bypass
• 4 = Occupied Standby
• 5 = Auto
MV2
Occupancy Status
None/None
All Units.
• 1 = Occupied
• 2 = Unoccupied
• 3 = Occupied Bypass
• 4 = Occupied Standby
• 5 = Unknown
MV4
Heat Cool Mode Status
All Units
• 1 = Auto
• 2 = Heat
• 3 = Morning Warm-up
• 4 = Cool
• 5 = Night Purge
• 6 = Pre Cool
• 7 = Off
MV7
Compressor Stage 3
Status
Units with 3+
Compressors
• 1 = Off
• 2 = On
• 3 = Not Present
MV8
Compressor Stage 4
Status
Units with 4 Compressors
• 1 = Off
• 2 = On
• 3 = Not Present