Table 10.
All object types sorted by object name (continued)
Object Type
Object Name
Min / Max
When the Point Exists
Description
AV37
Space Temperature
Setpoint Active
45 to 95 °F
Units that are Space
Control or Single Zone
VAV.
Actively used space
temperature setpoint.
AV25
Space Temperature
Setpoint BAS
-58 to 482 °F
Units that are Space
Control or Single Zone
VAV.
Communicated space
temperature setpoint.
AI20
Space Temperature
Setpoint Local
50 to 86 °F
Units with Thumbwheel
Installed.
Local thumbwheel input.
AV41
Supply Air Flow Active
0 – 15000 cfm
Units with Piezo Ring on
Supply Fan.
Actively used supply airflow.
AV39
Supply Air Flow Setpoint
0 – 7500 cfm
OAB or OAG units that are
208v or 460v.
Setpoint used to modulate the
indoor fan speed.
AI3
Supply Fan Pressure
Local
0 - 25 in(H
2
O)
Units with Piezo Ring on
Supply Fan.
Local supply fan piezo ring
pressure.
BO1
Supply Fan Start Stop
Command
All Units.
Normally Closed Input • 0 = On
• 1 = Off
BI1
Supply Fan Status
All Units.
Normally Closed Input • 0 = On
• 1 = Off
BV17
System LOCKOUT
All Units.
Latching diagnostic. Cleared
with Alarm Reset. • 0 = Normal
• 1 = Fail
BV28
Thumbwheel Installed
All Units.
• 0 = Not Installed • 1 =
Installed
BV23
Unoccupied Cooling
Mode
All Units.
• 0 = Disabled • 1 = Enabled
BV22
Unoccupied Cooling
Mode BAS
All Units.
• 0 = Disabled • 1 = Enabled
AV26
Unoccupied Cooling
Setpoint
60 – 90 °F
Units with Space
Temperature/Humidity
Sensor Installed.
Space cooling setpoint used in
unoccupied mode.
BV40
Unoccupied Dehumid
Mode
All Units.
• 0 = Disabled • 1 = Enabled
BV37
Unoccupied Dehumid
Mode BAS
All Units.
• 0 = Disabled • 1 = Enabled
AV28
Unoccupied Dewpoint
Setpoint
49 – 100 °F
Units with Space
Temperature/Humidity
Sensor Installed.
If the space dewpoint rises
above this setpoint during
unoccupied mode then
dehumidification will be
enabled.
BV39
Unoccupied Heating
Mode
All Units.
• 0 = Disabled • 1 = Enabled
BV38
Unoccupied Heating
Mode BAS
All Units.
• 0 = Disabled • 1 = Enabled
AV27
Unoccupied Heating
Setpoint
45 - 90 °F
Units with Space
Temperature/Humidity
Sensor Installed.
Space heating setpoint used in
unoccupied mode.
BV43
Ventilation Mode
Units that are Space
Control, Single Zone VAV,
or Discharge Control.
• 0 = Disabled
• 1 = Enabled
BI9
Water Coil Low Temp
Switch
Units that are Water
Source Heat Pump.
Normally closed input.
• 0 = Open
• 1 = Closed
BI8
Water Flow
Units that are Water
Source Heat Pump.
Normally open input.
• 0 = Off
• 1 = On
BV35
Y1 Space Lockout
Units that are Space
Control or Single Zone
VAV.
• 0 = Disabled
• 1 = Enabled
AI8
Zone CO
2
Local
0 – 3000
ppm
Units with a CO
2
Sensor
Installed.
Local Space CO
2
concentration