26
BAS-SVP18D-EN
Table 9. Multi-state values (continued)
Object Type
Object Name
Min / Max
When the Point
Exists
Description
MV9
Heat Type
None/None
All Units
• 1 = No Heat
• 2 = Indirect Fired Gas Heat
• 3 = Electric Heat
• 4 = Other
• 5 = Direct Fired Gas Heat
• 6 = Hot Water/Steam
MV13
Program Control Type
All Units.
• 1 = Space Control
• 2 = Discharge Control
• 3 = Single Zone VAV
• 4 = Multi Zone VAV
MV16
Dehumidification System
Status
All Units.
• 1 = Off
• 2 = On
• 3 = Not Present
MV21
Compressor Stage 1
Status
Units with 1+
Compressors.
• 1 = Off
• 2 = On
• 3 = Not Present
MV22
Compressor Stage 2
Status
Units with 2+
Compressors.
• 1 = Off
• 2 = On
• 3 = Not Present
Table 10.
All object types sorted by object name
Object Type
Object Name
Min / Max
When the Point Exists
Description
BV16
Alarm Reset
All Units.
1 = Reset diagnostics or
lockouts. This will reset ALL
diagnostics or lockouts. If the
condition still exists, the
diagnostic reoccurs.
BV7
Auxiliary Heating Mode
Units that are Heat Pump.
• 0 = Disabled
• 1 = Enabled
AI4
Circuit 1 Condenser
Coil Temperature Local
-50 to 200 °F
Units with Head
Pressure Control or an Air
Source Heat Pump.
Local condenser coil
temperature sensor on circuit
1.
AO3
Circuit 1 Digital Scroll/
Variable Speed
Command
0 - 100%
Units with Digital Scroll or
Variable Speed on the first
circuit.
Analog digital scroll or variable
speed output command.
AI18
Circuit 1 Liquid Line
Pressure Local
0 – 500 psi
Units with Head Pressure
Control and is an Air
Source Heat Pump.
Local refrigerant pressure
sensor on circuit 1.
BO16
Circuit 1 Reversing Valve
Units that are Heat Pump.
• 0 = Off
• 1 = On
AI5
Circuit 2 Condenser Coil
Temperature Local
-50 -200 °F
Units with Head Pressure
Control or an Air Source
Heat Pump.
Local condenser coil
temperature sensor on circuit
2.
AO8
Circuit 2 Digital Scroll/
Variable Speed
Command
0 - 100%
Units with Digital Scroll or
Variable Speed on the
second circuit.
Analog digital scroll or variable
speed output command.
AI19
Circuit 2 Liquid Line
Pressure Local
0 – 500 psi
Units with Head Pressure
Control and is an Air
Source Heat Pump.
Local refrigerant pressure
sensor on circuit 2.
BO17
Circuit 2 Reversing Valve
Units that are Heat Pump
and Two Circuits.
• 0 = Off
• 1 = On
BO11
Compressor 1 Command
Units with 1+
Compressors.
• 0 = Off
• 1 = On
BO12
Compressor 2 Command
Units with 2+
Compressors.
• 0 = Off
• 1 = On
BO5
Compressor 3 Command
Units with 3+
Compressors.
• 0 = Off
• 1 = On
BO6
Compressor 4 Command
Units with 4+
Compressors.
• 0 = Off
• 1 = On
AV31
Compressor Count
0 - 4
Units with DX Cooling.
Number of compressors
installed in the unit.
AV18
Compressor Heating
Capacity
0 - 100%
Units that are Air Source
or Water Source Heat
Pumps.
Compressor Heating source
capacity.