BAS-SVP18D-EN
27
Table 10.
All object types sorted by object name (continued)
Object Type
Object Name
Min / Max
When the Point Exists
Description
BV25
Compressor Stage 1
Request
Units with 1+
Compressors.
• 0 = Off
• 1 = On
MV21
Compressor Stage 1
Status
Units with 1+
Compressors.
• 1 = Off
• 2 = On
• 3 = Not Present
BV29
Compressor Stage 2
Request
Units with 2+
Compressors.
• 0 = Off
• 1 = On
MV22
Compressor Stage 2
Status
Units with 2+
Compressors.
• 1 = Off
• 2 = On
• 3 = Not Present
BV30
Compressor Stage 3
Request
Units with 3+
Compressors.
• 0 = Off
• 1 = On
MV7
Compressor Stage 3
Status
Units with 3+
Compressors
• 1 = Off
• 2 = On
• 3 = Not Present
BV31
Compressor Stage 4
Request
Units with 4 Compressors.
• 0 = Off
• 1 = On
MV8
Compressor Stage 4
Status
Units with 4 Compressors
• 1 = Off
• 2 = On
• 3 = Not Present
AV24
Condenser Coil
Temperature Setpoint
80 – 125 °F
Units with Head Pressure
Control and isn't an Air
Source Heat Pump.
Temperature setpoint used to
modulate condenser fan(s).
BO14
Condenser Fan
Command
Units with Sound
Attenuation Package or is
an Air Source Heat Pump.
• 0 = Off
• 1 = On
AO7
Condenser Fan Speed
Command
0 - 100%
Units with Head Pressure
Control.
Analog condenser fan speed
command
AV52
Cooling Capacity
0 - 100%
Units with DX Cooling.
Primary cooling source
capacity.
BV26
Cooling Lockout BAS
Units with DX Cooling.
• 0 = Normal
• 1 = Lockout
AV6
DAT High Temp Cutout
90 – 130 °F
All Units.
If the discharge air
temperature is greater than
the discharge air high limit for
(AV16) minutes, the controller
signals an alarm
and shuts down the unit.
AV15
DAT Low Temp Cutout
35 – 50 °F
All Units.
If the discharge air
temperature is less than the
discharge air low limit for
(AV16) minutes, the controller
signals an alarm and
shuts down the unit.
AV16
DAT Temp Cutout Time
10 - 25
All Units.
Time required for low limit or
high limit temperature to
signal alarm.
BV4
Defrost Mode
Units that are Heat Pump.
• 0 = Disabled
• 1 = Enabled
BV27
Dehumidification
Command
Units that are Space
Control, Single Zone
VAV, or Discharge Control.
• 0 = Disabled
• 1 = Enabled
MV16
Dehumidification System
Status
All Units.
• 1 = Off
• 2 = On
• 3 = Not Present
BV6
Diagnostic: Discharge Air
Temperature Source
Failure
All Units.
Auto-Reset diagnostic.
• 0 = Normal
• 1 = Fail
BV36
Diagnostic: Duct Static
Pressure Failure
Units that are Multi Zone
VAV.
Auto-Reset diagnostic.
• 0 = Normal
• 1 = Fail
BV32
Diagnostic: ERV Leaving
Air Conditions Failure
Units that are Water
Source Heat Pump with an
ERV.
Auto-Reset diagnostic.
• 0 = Normal
• 1 = Fail
BV34
Diagnostic: Evap Temp
Source Failure
Units with DX Cooling.
Auto-Reset diagnostic.
• 0 = Normal
• 1 = Fail
BV42
Diagnostic: Heat Failure
Units with Gas as the
Primary Heat.
Auto-Reset diagnostic.
• 0 = Normal
• 1 = Fail
BV3
Diagnostic: OAD Proving
Switch
All Units.
Latching diagnostic. Cleared
with Alarm Reset.
• 0 = Normal
• 1 = Fail
BV14
Diagnostic: Outdoor Air
Humidity Source Failure
All Units.
Auto-Reset diagnostic.
• 0 = Normal
• 1 = Fail