Table 10.

All object types sorted by object name (continued)

Object Type

Object Name

Min / Max

When the Point Exists

Description

BV25

Compressor Stage 1
Request

Units with 1+
Compressors.

• 0 = Off
• 1 = On

MV21

Compressor Stage 1
Status

Units with 1+
Compressors.

• 1 = Off
• 2 = On
• 3 = Not Present

BV29

Compressor Stage 2
Request

Units with 2+
Compressors.

• 0 = Off
• 1 = On

MV22

Compressor Stage 2
Status

Units with 2+
Compressors.

• 1 = Off
• 2 = On
• 3 = Not Present

BV30

Compressor Stage 3
Request

Units with 3+
Compressors.

• 0 = Off
• 1 = On

MV7

Compressor Stage 3
Status

Units with 3+
Compressors

• 1 = Off
• 2 = On
• 3 = Not Present

BV31

Compressor Stage 4
Request

Units with 4 Compressors.

• 0 = Off
• 1 = On

MV8

Compressor Stage 4
Status

Units with 4 Compressors

• 1 = Off
• 2 = On
• 3 = Not Present

AV24

Condenser Coil
Temperature Setpoint

80 – 125 °F

Units with Head Pressure
Control and isn't an Air
Source Heat Pump.

Temperature setpoint used to
modulate condenser fan(s).

BO14

Condenser Fan
Command

Units with Sound
Attenuation Package or is
an Air Source Heat Pump.

• 0 = Off
• 1 = On

AO7

Condenser Fan Speed
Command

0 - 100%

Units with Head Pressure
Control.

Analog condenser fan speed
command

AV52

Cooling Capacity

0 - 100%

Units with DX Cooling.

Primary cooling source
capacity.

BV26

Cooling Lockout BAS

Units with DX Cooling.

• 0 = Normal
• 1 = Lockout

AV6

DAT High Temp Cutout

90 – 130 °F

All Units.

If the discharge air
temperature is greater than
the discharge air high limit for
(AV16) minutes, the controller
signals an alarm
and shuts down the unit.

AV15

DAT Low Temp Cutout

35 – 50 °F

All Units.

If the discharge air
temperature is less than the
discharge air low limit for
(AV16) minutes, the controller
signals an alarm and
shuts down the unit.

AV16

DAT Temp Cutout Time

10 - 25

All Units.

Time required for low limit or
high limit temperature to
signal alarm.

BV4

Defrost Mode

Units that are Heat Pump.

• 0 = Disabled
• 1 = Enabled

BV27

Dehumidification
Command

Units that are Space
Control, Single Zone
VAV, or Discharge Control.

• 0 = Disabled
• 1 = Enabled

MV16

Dehumidification System
Status

All Units.

• 1 = Off
• 2 = On
• 3 = Not Present

BV6

Diagnostic: Discharge Air
Temperature Source
Failure

All Units.

Auto-Reset diagnostic.
• 0 = Normal
• 1 = Fail

BV36

Diagnostic: Duct Static
Pressure Failure

Units that are Multi Zone
VAV.

Auto-Reset diagnostic.
• 0 = Normal
• 1 = Fail

BV32

Diagnostic: ERV Leaving
Air Conditions Failure

Units that are Water
Source Heat Pump with an
ERV.

Auto-Reset diagnostic.
• 0 = Normal
• 1 = Fail

BV34

Diagnostic: Evap Temp
Source Failure

Units with DX Cooling.

Auto-Reset diagnostic.
• 0 = Normal
• 1 = Fail

BV42

Diagnostic: Heat Failure

Units with Gas as the
Primary Heat.

Auto-Reset diagnostic.
• 0 = Normal
• 1 = Fail

BV3

Diagnostic: OAD Proving
Switch

All Units.

Latching diagnostic. Cleared
with Alarm Reset.
• 0 = Normal
• 1 = Fail

BV14

Diagnostic: Outdoor Air
Humidity Source Failure

All Units.

Auto-Reset diagnostic.
• 0 = Normal
• 1 = Fail

O

Ob

bjje

ecctt a

an

nd

d D

Diia

ag

gn

no

ossttiicc D

Da

atta

a P

Po

oiin

nttss

Содержание Tracer UC600

Страница 1: ...uires specific knowledge and training Improperly installed adjusted or altered equipment by an unqualified person could result in death or serious injury When working on the equipment observe all prec...

Страница 2: ...ctices are important to the environment our customers and the air conditioning industry All technicians who handle refrigerants must be certified according to local rules For the USA the Federal Clean...

Страница 3: ...o of f e en ne er rg gi iz ze ed d e el le ec ct tr ri ic ca al l c co on nt ta ac ct t a ar rc c o or r f fl la as sh h t te ec ch hn ni ic ci ia an ns s M MU US ST T p pu ut t o on n a al ll l P PP...

Страница 4: ...0 3rd Party BAS Integration 10 Tracer SC BAS Integration 11 BAS Unit Control 11 Initiating System Control 12 Routinely Updating BAS Values 12 Alarm Reset 12 BACnet Data Points and Configuration Proper...

Страница 5: ...utomation and Control Network BACnet protocol is ANSI ASHRAE Standard 135 This standard allows building automation systems or components from different manufacturers to share information and control f...

Страница 6: ...RX TX UC600 ADDRESS 0 1 2 3 4 5 6 7 8 9 x1 0 1 2 3 4 5 6 7 8 9 x10 0 1 2 3 4 5 6 7 8 9 x100 BO4 BO3 BO2 BO1 ADDRESS 0 1 2 3 4 5 6 7 8 9 x1 0 1 2 3 4 5 6 7 8 9 x10 0 1 2 3 4 5 6 7 8 9 x100 Rotary switc...

Страница 7: ...on solid yellow Reverse polarity is present LED not illuminated The controller is not detecting communication Cycle the power to re establish communication Verify that the controller is capable of com...

Страница 8: ...8 BAS SVP18D EN U UC C6 60 00 0 R Ro ot ta ar ry y S Sw wi it tc ch he es s a an nd d L LE ED Ds s...

Страница 9: ...on USB cable radio button if it is not already selected 4 Click the Connect button and the Unit Summary page displays after successful connection Configuration At the Unit Summary page 1 Enter a meani...

Страница 10: ...e ID box and enter a BACnet Device ID 8 Click Save 9 Cycle power to the device to have the new value take effect MS TP MAC Address Each device on a BACnet MS TP network must be assigned a unique physi...

Страница 11: ...e the new value take effect N No ot te e When the software method is enabled the hardware method is automatically disabled Figure 3 Example showing rotary dial settings and the BACnet device ID Tracer...

Страница 12: ...itions This may result in decreased occupant comfort and damage to building systems Alarm Reset The UC600 control system monitors the operation of the HVAC equipment If an abnormal condition is detect...

Страница 13: ...TP communications interface for Trane IntelliPak ReliaTel and CH530 controls Standardized Device Profile Annex L Profile Description Supported Profile BACnet Advanced Application Controller B AAC BAC...

Страница 14: ...t_State Out_Of_Service Units Object_Name Description Out_Of_Service Present_Value Reliability Min_Pres_Value Max_Pres_Value COV_Increment Time_Delay Notification_Class High_Limit Low_Limit Deadband Li...

Страница 15: ...able Polarity Notify_Type Description Inactive_Text Active_Text Change_Of_State_Time Change_Of_State_Count Time_Of_State_Count_ Reset Elapsed_Active_Time Time_Of_Active_Time_ Reset Time_Delay Notifica...

Страница 16: ..._Status Vendor_Name Vendor_Identifier Model_Name Firmware_Revision Application_Software_ Version Protocol_Version Protocol_Revision Protocol_Services_ Supported Protocol_Object_Types_ Supported Object...

Страница 17: ...Object_Type Present_Value Status_Flags Event_State Out_Of_Service Number_Of_States Object_Name Description State_Text Out_Of_Service Present_Value Reliability Priority_Array Relinquish_Default Time_De...

Страница 18: ...e 10 Baud Rate s 9600 19200 38400 Device Address Binding Device Address Binding Supported Static Device Binding Supported Networking Options Networking Descriptions Supported Option Annex H BACnet Tun...

Страница 19: ...flow Monitoring Local outside air flow AI11 Discharge Air Temperature Local 25 to 135 F All Units Local discharge air temperature sensor AI12 Return Duct Space Pressure Local 0 2 in H2O Units with Pow...

Страница 20: ...4 Discharge Air Temperature BAS 10 to 150 F All Units Communicated discharge air temperature AV5 Discharge Air Temperature Active 10 to 150 F All Units Actively used discharge air temperature AV6 DAT...

Страница 21: ...100 F Units with Discharge Air Control Discharge air setpoing during heating mode AV33 Outdoor Air Heating Setpoint OAHS 40 75 F Units with Space Control Discharge Control or Single Zone VAV Setpoint...

Страница 22: ...tic Pressure Active 6 to 6 in H2O Units with Multi Zone VAV Actively used duct static pressure AV66 Discharge Air Temperature Setpoint Active 38 130 F Units with Multi Zone VAV Actively used discharge...

Страница 23: ...BO2 Outdoor Air Damper Command All Units 0 Open 1 Closed BO3 Heat 1 Command Units with Primary Heat 0 Off 1 On BO4 Inducer Command Units with Gas as the Primary Heat 0 Off 1 On BO5 Compressor 3 Comman...

Страница 24: ...gnostic Space Humidity Source Failure Units that are Space Control or Single Zone VAV Auto Reset diagnostic 0 Normal 1 Fail BV13 Diagnostic Outdoor Air Temperature Source Failure All Units Auto Reset...

Страница 25: ...ic Pressure Failure Units that are Multi Zone VAV Auto Reset diagnostic 0 Normal 1 Fail BV37 Unoccupied Dehumid Mode BAS All Units 0 Disabled 1 Enabled BV38 Unoccupied Heating Mode BAS All Units 0 Dis...

Страница 26: ...nalog digital scroll or variable speed output command AI18 Circuit 1 Liquid Line Pressure Local 0 500 psi Units with Head Pressure Control and is an Air Source Heat Pump Local refrigerant pressure sen...

Страница 27: ...erature is greater than the discharge air high limit for AV16 minutes the controller signals an alarm and shuts down the unit AV15 DAT Low Temp Cutout 35 50 F All Units If the discharge air temperatur...

Страница 28: ...e air temperature setpoint AV65 Duct Static Pressure Active 6 to 6 in H2O Units with Multi Zone VAV Actively used duct static pressure AV64 Duct Static Pressure BAS 6 to 6 in H2O Units with Multi Zone...

Страница 29: ...Gas Heat 6 Hot Water Steam AV69 Heat Cool Mode Deadband 58 to 482 F Units with Multi Zone VAV Heat is enabled when Outdoor Air Temperature drops below Discharge Temperature Setpoint Heat Cool Mode Dea...

Страница 30: ...l Installed Time that Unoccupied Mode is delayed when Occupied Button is pressed AV1 Occupied Cooling Setpoint 55 85 F Units with Space Control or Single Zone VAV Space cooling setpoint used in occupi...

Страница 31: ...All Units 1 Space Control 2 Discharge Control 3 Single Zone VAV 4 Multi Zone VAV BV18 Return Air Damper Option All Units 0 Not Installed 1 Installed AI14 Return Air Humidity Local 0 100 Units with Mod...

Страница 32: ...0 Disabled 1 Enabled BV22 Unoccupied Cooling Mode BAS All Units 0 Disabled 1 Enabled AV26 Unoccupied Cooling Setpoint 60 90 F Units with Space Temperature Humidity Sensor Installed Space cooling setpo...

Страница 33: ...red with Alarm Reset or power cycle 2 BV11 Diagnostic Space Temperature Source Failure 0 Normal 1 Fail Latching diagnostic Cleared with Alarm Reset or power cycle 2 BV12 Diagnostic Space Humidity Sour...

Страница 34: ...pplication Guide BAS APG008 Tracer TU Online Help Tracer TU Service Tool Getting Started Guide TTU SVN01 Tracer UC600 Installation Instructions X39641178 01 Tracer XM30 Expansion Module Installation I...

Страница 35: ...BAS SVP18D EN 35 N No ot te es s...

Страница 36: ...For more information please visit trane com or tranetechnologies com Trane has a policy of continuous product and product data improvements and reserves the right to change design and specifications w...

Отзывы: