Table 4. Analog outputs (continued)
Object Type
Object Name
Min / Max
When the Point Exists
Description
AO3
Circuit 1 Digital Scroll/
Variable Speed
Command
0 - 100%
Units with Digital Scroll or
Variable Speed on the first
circuit.
Analog digital scroll or variable
speed output command.
AO4
PEVFD Command
0 - 100%
Units with Powered
Exhaust.
Analog exhaust fan VFD
speed.
AO5
OAD Position Command
0 - 100%
Units with Modulating
Dampers.
Analog outdoor air damper
command.
AO6
ERV Bypass Position
Command
0 - 100%
Units with ERV.
Analog ERV bypass damper
command.
AO7
Condenser Fan Speed
Command
0 - 100%
Units with Head Pressure
Control.
Analog condenser fan speed
command
AO8
Circuit 2 Digital Scroll/
Variable Speed
Command
0 - 100%
Units with Digital Scroll or
Variable Speed on the
second circuit.
Analog digital scroll or variable
speed output command.
AO11
Heating Output
Command
0 - 100%
Units with any type of
Primary Heat.
Analog heating output
command.
Table 5. Analog values
Object Type
Object Name
Min / Max
When the Point Exists
Description
AV1
Occupied Cooling
Setpoint
55 – 85 °F
Units with Space Control
or Single Zone VAV.
Space cooling setpoint used in
occupied mode.
AV2
Occupied Heating
Setpoint
55 – 85 °F
Units with Space Control
or Single Zone VAV.
Space heating setpoint used in
occupied mode.
AV3
Occupied Offset
0.5 – 30 Δ °F
All Units.
The value used to calculate the
heating/cooling setpoints in
occupied mode. If the unit has
a thumbwheel installed
Occupied Offset defaults to 2.
• Active heating setpoint =
active setpoint – occupied
offset.
• Active cooling setpoint =
active se occupied
offset.
AV4
Discharge Air
Temperature BAS
-10 to 150 °F
All Units.
Communicated discharge air
temperature.
AV5
Discharge Air
Temperature Active
-10 to 150 °F
All Units.
Actively used discharge air
temperature.
AV6
DAT High Temp Cutout
90 – 130 °F
All Units.
If the discharge air
temperature is greater than
the discharge air high limit for
(AV16) minutes, the controller
signals an alarm and shuts
down the unit.
AV7
Space RH Active
-150 to 150%
Units with Space Humidity
Sensor Installed.
Actively used space relative
humidity.
AV8
Space RH BAS
-150 to 150%
All Units.
Communicated space relative
humidity.
AV9
Occupied Bypass Time
2 - 360
Units with Thumbwheel
Installed.
Time that Unoccupied Mode is
delayed when Occupied Button
is pressed.
AV10
Outdoor Air Dewpoint
Setpoint (OADS)
49 – 100 °F
Units with Space Control,
Discharge Control, or
Single Zone VAV.
If the outdoor air dewpoint is
greater than OADS, the unit
will enable dehumidification.
AV11
Outdoor Air Dewpoint
Active
-10 to 150 °F
All Units.
Dewpoint of the outdoor air.
This point is calculated within
the program.
AV12
Liquid Line Pressure
Setpoint
200 – 600 psi
Air Source Heat Pumps
with Head Pressure
Control.
Pressure setpoint used to
modulate condenser fan(s).
AV13
Outdoor Air Minimum
Flow Setpoint BAS
0 – 13500 cfm
VAV Units with Outdoor air
flow Monitoring and
Modulating Dampers.
air flow setpoint used to
modulate dampers.
AV14
Evaporator Leaving
Temperature Setpoint
45 – 75 °F
All Units.
Evaporator leaving air
temperature setpoint during
dehumidification mode or
Single Zone VAV
AV15
DAT Low Temp Cutout
35 – 50 °F
All Units.
If the discharge air
temperature is less than the
discharge air low limit for
(AV16) minutes, the controller
signals an alarm and shuts
down the unit.