© Copyright Muuntosähkö Oy – Trafox
Superintend IMD
12
R
Device alarm and status
register
uint16
none
Bit mask:
0x0001 = a fault or alarm related to insulation
resistance, corresponds to the INSULATION alarm
LED of the local user interface
0x0002 = insulation resistance pre-alarm
0x0004 = system test fault
0x0008 = fault in the M1 or M2 wire
0x0010 = fault in the TG or MG wire
0x0020 = load alarm
0x0040 = PE fault
0x0080 = temperature alarm
0x0100 = system test active
0x0200 = internal calibration active (the insulation
level measurement values are invalid)
the statuses remain active until their cause has been
eliminated
13
R/
W
Start of the device system test
uint16
none
Start of the system test. Value 1 starts the test,
other values are not taken into account. IM-01.MED
resets the request after reading it.
14
R/
W
Start of the resistance
measurement of the PEC-01
units connected to the device
uint16
none
Start of the resistance measurement of the PE units.
Value 1 starts the measurement, other values are not
taken into account. IM-01.MED resets the request
after reading it.
15
R/
W
Joint acknowledgement of
alarms
uint16
none
Joint acknowledgement of unacknowledged alarms.
Value 1 acknowledges all alarms, other values are not
taken into account. IM-01.MED resets the request
after reading it. This does not acknowledge/inactivate
active alarms.
16
R
The lowest allowed value of the
limit parameter of the insulation
resistance alarm
uint16
kOh
m
50
17
R
The highest allowed value of the
limit parameter of the insulation
resistance alarm
uint16
kOh
m
1000
18
R
The resolution (jog) of the limit
parameter of the insulation
resistance alarm
uint16
kOh
m
50
19
R
The lowest allowed value of the
limit parameter of the insulation
resistance pre-alarm
uint16
%
100
20
R
The highest allowed value of the
limit parameter of the insulation
resistance pre-alarm
uint16
%
200
21
R
The resolution (jog) of the limit
parameter of the insulation
resistance pre-alarm
uint16
%
10
22
R
The lowest allowed value of the
limit parameter of the load
alarm
uint16
%
50, with an exception of value 0, which sets the
alarm function to OFF mode
23
R
The highest allowed value of the
limit parameter of the load
alarm
uint16
%
100
24
R
The resolution (jog) of the limit
parameter of the load alarm
uint16
%
5
25
R
The lowest allowed value of the
limit parameter of the
temperature alarm
uint16
°C
30, with an exception of value 0, which sets the
alarm function to OFF mode
26
R
The highest allowed value of the
limit parameter of the
temperature alarm
uint16
°C
140
27
R
The resolution (jog) of the limit
parameter of the temperature
alarm
uint16
°C
5
28
R
The nominal value of the
current transformer, the lowest
allowed value of the device
parameter
uint16
A
10
29
R
The nominal value of the
current transformer, the highest
uint16
A
100
Содержание SUPERINTEND IC-01
Страница 8: ...8 Copyright Muuntosähkö Oy Trafox Superintend IMD http www trafox fi Figure 1 System connection ...
Страница 21: ...Superintend IMD Copyright Muuntosähkö Oy Trafox 21 http www trafox fi ...
Страница 23: ...Superintend IMD Copyright Muuntosähkö Oy Trafox 23 http www trafox fi ...
Страница 28: ...28 Copyright Muuntosähkö Oy Trafox Superintend IMD http www trafox fi ...
Страница 35: ...Superintend IMD Copyright Muuntosähkö Oy Trafox 35 http www trafox fi ...
Страница 37: ...Superintend IMD Copyright Muuntosähkö Oy Trafox 37 http www trafox fi ...
Страница 70: ...70 Copyright Muuntosähkö Oy Trafox Superintend IMD http www trafox fi 36 3 mm 110 mm 62 mm ...