The most important alarms are indicated by a red LED light, which BLINKS in fault
situations and is on STEADILY if the fault has been fixed but not acknowledged (the OLD
ALRM mode).
When navigating the menu, the warning LED lights indicate which menu item is in use.
The insulation resistance fault activates IMMEDIATELY when the measured parameter
drops below the alarm limit. The delay set for the alarms applies to all faults except the
insulation resistance measurement. The value to be measured must consistently be
above the alarm limit for the length of the delay before an alarm is given. If the
measured quantity drops below the alarm limit during the delay, time counting restarts.
In addition, all alarms have a five-percent hysteresis. In other words, an alarm becomes
active when the set limit is reached, but it is deactivated only when the measured value
deviates by 5% in a safe direction from the limit given.
The screen mode of each parameter
alternately displays the following:
On the top row, the value / fault limit of the parameter that caused the fault, and
on the bottom row, the current status: OK, ALARM or OLD ALRM
Fault start time and date
If the fault has been deactivated and becomes active again, the start time of the active
fault is displayed. In items InstUnit, WireAmpl and WireOffs, there may be several
faults, which are displayed one after the other. In the OK mode, nothing is displayed in
the screen mode.
The screen always displays the smallest value (insulation resistance) or largest (all other
measurements) value / fault limit measured during the fault first, followed by the fault
start time.
The temperature alarm has been deactivated but not
acknowledged.
The largest value measured during the fault, the alarm limit's set
value and the fault start time are displayed.
The temperature alarm is active.
The highest temperature measured during the fault is 93
degrees and the alarm limit is 90 degrees.
Содержание SUPERINTEND IC-01
Страница 8: ...8 Copyright Muuntosähkö Oy Trafox Superintend IMD http www trafox fi Figure 1 System connection ...
Страница 21: ...Superintend IMD Copyright Muuntosähkö Oy Trafox 21 http www trafox fi ...
Страница 23: ...Superintend IMD Copyright Muuntosähkö Oy Trafox 23 http www trafox fi ...
Страница 28: ...28 Copyright Muuntosähkö Oy Trafox Superintend IMD http www trafox fi ...
Страница 35: ...Superintend IMD Copyright Muuntosähkö Oy Trafox 35 http www trafox fi ...
Страница 37: ...Superintend IMD Copyright Muuntosähkö Oy Trafox 37 http www trafox fi ...
Страница 70: ...70 Copyright Muuntosähkö Oy Trafox Superintend IMD http www trafox fi 36 3 mm 110 mm 62 mm ...