48
© Copyright Muuntosähkö Oy – Trafox
Superintend IMD
Setup log (SETUPLOG.TXT)
The setup log is a file in which ALL system parameters which the user can change in the
Setup menu are entered. The Setup menu passcode is the only exception. It cannot be
changed in the Setup menu but is always read from the card during start-up. The
passcode default is always 123, which also works when the card cannot be read. If you
want to change the passcode, the file must be changed.
A new row is added to the file only if the user changes a system parameter, or a new
SETUPLOG.TXT file is created. The most recent parameter values are entered on the new
row.
The data is written in the file in the following order:
[TIME][Password][InsLimit][PreInsLim][AlarmDly][Temp Lim][Load
Lim][TC/IC/PE/RD][PEresist][TranSize][Nom.Cur][AUXalarm]
[TIME] = time stamp
[Password] = the passcode of the Setup menu
The field format is PW=
NNN
, where
NNN
is a three-digit ID code.
The ID code cannot be changed in the Setup menu; in the file, the value
NNN
must be changed.
A new passcode will only become valid at the start-up.
The passcode read at the start-up will be valid until the next start-up.
[InsLimit] = the limit value of the insulation resistance alarm (kOhms)
[PreInsLim] = the limit value of the pre-alarm of the insulation resistance measurement
(percentage)
[AlarmDly] = measurement alarm delay (seconds), not applicable to the insulation
resistance measurement
[Temp Lim] = the limit value of temperature alarms (transformer, device) (in
Centigrade)
[Load Lim] = the limit value of load measurement (percentage of the nominal load of the
isolation transformer)
[TC/IC/PE/RD] = the latest approved configuration at the unit level
[PEresist] = the limit value of the PE channel resistance measurement (percentage)
[TranSize] = the provided nominal primary/secondary current of the current transformer
(amperes)
[Nom.Cur] = the provided nominal current of the isolation transformer (amperes)
[AUXalarm] = a configuration of alarms that will activate the AUX alarm relay
Содержание SUPERINTEND IC-01
Страница 8: ...8 Copyright Muuntosähkö Oy Trafox Superintend IMD http www trafox fi Figure 1 System connection ...
Страница 21: ...Superintend IMD Copyright Muuntosähkö Oy Trafox 21 http www trafox fi ...
Страница 23: ...Superintend IMD Copyright Muuntosähkö Oy Trafox 23 http www trafox fi ...
Страница 28: ...28 Copyright Muuntosähkö Oy Trafox Superintend IMD http www trafox fi ...
Страница 35: ...Superintend IMD Copyright Muuntosähkö Oy Trafox 35 http www trafox fi ...
Страница 37: ...Superintend IMD Copyright Muuntosähkö Oy Trafox 37 http www trafox fi ...
Страница 70: ...70 Copyright Muuntosähkö Oy Trafox Superintend IMD http www trafox fi 36 3 mm 110 mm 62 mm ...