Superintend IMD
© Copyright Muuntosähkö Oy - Trafox
43
Measure Failure OFF
The insulation resistance
measurement can be
performed after an internal
fault has been corrected.
Wire Ampl Test Fail [
N
][
L
]
The Wire Test amplitude is too
low (
N
, whereas the alarm
limit is
L
) -> M1 has been
disconnected from the network
to be measured.
Wire Ampl Test OK
The Wire Test amplitude has
recovered to the correct level;
M1’s connection to the network
to be measured has been
restored.
Wire Offset Test Fail [
N
ADP][
L
ADP]
The Wire Test offset is too
small (
N
, whereas the alarm
limit is
L
) -> M1 or M2 has
been disconnected from the
network to be measured.
Wire Offset Test OK
The Wire Test offset has
recovered to the correct level;
the M1 and M2 connections to
the network to be measured
have been restored.
Too much noise [
N
%][
L
%]
The insulation resistance
measurement continuously has
a noise level too high (N)
whereas the alarm limit is
L
.
Noise normal level
The noise level of the
insulation resistance
measurement has returned to
normal.
PE Alarm ON [PE
XX
CH
CC
][
N
][
L
]
The resistance fault of channel
CC
of the PEC-01 unit in the PE
address of
XX
has been
activated with value
N
,
whereas the limit value has
been
L
.
PE Alarm OFF [PE
XX
CH
CC
]
The resistance fault of channel
CC
of the PEC-01 unit in the PE
address of
XX
is no longer
active.
PE Alarm Acknowledge [PE
XX
CH
CC
]
The resistance fault of channel
CC
of the PEC-01 unit in the PE
address XX is no longer active.
The alarm was acknowledged
manually.
Alarm Limit changed [PEresist] [
L1
%]->[
L2
%]
The limit value of the
resistance fault of the PEC-01
units was changed from
L1
to
L2.
Missing TC Alarm ON [TC
XX
]
The TC-01 unit configured in
the TC address
XX
is not
responding.
Missing TC Alarm OFF [TC
XX
]
The TC-01 unit configured in
TC address
XX
is responding
Содержание SUPERINTEND IC-01
Страница 8: ...8 Copyright Muuntosähkö Oy Trafox Superintend IMD http www trafox fi Figure 1 System connection ...
Страница 21: ...Superintend IMD Copyright Muuntosähkö Oy Trafox 21 http www trafox fi ...
Страница 23: ...Superintend IMD Copyright Muuntosähkö Oy Trafox 23 http www trafox fi ...
Страница 28: ...28 Copyright Muuntosähkö Oy Trafox Superintend IMD http www trafox fi ...