Set the alarm parameters (SETUP
→
InsLimit, PrInsLim, Temp Lim, TsensTyp (Pt
Calib, if needed), LoadLim, PEalarm%, AlarmDly). Remember to disable TempLim
if temperature measurement has not been connected and to disable LoadLim if
the load current measurement has not been connected.
Set the AUX. ALARM mask (SETUP
→
AUXalarm), which defines the faults that
cause the AUX. ALARM relay to trigger.
Perform bus scanning using the menu SETUP
→
Network Scan. ENSURE that all
installed units (IC, TC, RD, PEC) are identified and have the correct addresses,
and that the measured PE resistances correspond to the physical lengths of the
installed earthing wires.
During network scanning, the resistances from all channels of all PEC-01
units connected to the system are measured. Therefore, performing a
Network Scan / Network View is permitted in medical locations only when
there is no activity in the premises to be monitored.
When needed, set the range for CLT-01 unit’s current loop output
(SETUP
→
LoopCurr)
When needed, set the TCP/IP parameters (SETUP
→
IP Settings)
A more detailed description of the configuration is provided in the Manual section “SETUP
menu”.
Содержание SUPERINTEND IC-01
Страница 8: ...8 Copyright Muuntosähkö Oy Trafox Superintend IMD http www trafox fi Figure 1 System connection ...
Страница 21: ...Superintend IMD Copyright Muuntosähkö Oy Trafox 21 http www trafox fi ...
Страница 23: ...Superintend IMD Copyright Muuntosähkö Oy Trafox 23 http www trafox fi ...
Страница 28: ...28 Copyright Muuntosähkö Oy Trafox Superintend IMD http www trafox fi ...
Страница 35: ...Superintend IMD Copyright Muuntosähkö Oy Trafox 35 http www trafox fi ...
Страница 37: ...Superintend IMD Copyright Muuntosähkö Oy Trafox 37 http www trafox fi ...
Страница 70: ...70 Copyright Muuntosähkö Oy Trafox Superintend IMD http www trafox fi 36 3 mm 110 mm 62 mm ...