Superintend IMD
The RS-485 connection is made using a 2*2 twisted paired cable equipped with a shield
(e.g. AWG22=0.32 mm²=106 Ω/km). In that case, the maximum length of the chain
from the IM-01.MED unit to the last remote unit is 500 m. If a thinner cable is used, the
allowed length shortens inversely proportionately to the cable resistance. The cable
shield is connected to the SH terminal of each unit. The shield is connected to the
network protective earth in the IM-01.MED unit. In other devices, the shields are floating
and the connector only functions as a joining connector of two shields. The twisted pairs
are connected so that the A–B signals are in one pair and the +12V–earth are in another
pair.
Examples of network connection. In the upper Figure, the IM-01.MED unit is in
the middle of the chain, and in the lower Figure, it is at the end of the chain.
Terminators are installed in the green units.
Checklist for the installation of the bus:
Each unit of the same type must have a unique address.
No more than two RS-485 cables may be installed in any unit. Otherwise, the bus
does not form an uninterrupted chain but has branches.
The shields of the cables are connected to the SH terminal of each unit.
Содержание SUPERINTEND IC-01
Страница 8: ...8 Copyright Muuntosähkö Oy Trafox Superintend IMD http www trafox fi Figure 1 System connection ...
Страница 21: ...Superintend IMD Copyright Muuntosähkö Oy Trafox 21 http www trafox fi ...
Страница 23: ...Superintend IMD Copyright Muuntosähkö Oy Trafox 23 http www trafox fi ...
Страница 28: ...28 Copyright Muuntosähkö Oy Trafox Superintend IMD http www trafox fi ...
Страница 35: ...Superintend IMD Copyright Muuntosähkö Oy Trafox 35 http www trafox fi ...
Страница 37: ...Superintend IMD Copyright Muuntosähkö Oy Trafox 37 http www trafox fi ...
Страница 70: ...70 Copyright Muuntosähkö Oy Trafox Superintend IMD http www trafox fi 36 3 mm 110 mm 62 mm ...