47
Measurement log (MEASLOG.TXT)
The measurement log
is used to store all measured data every hour on the hour. In
addition, data is always saved when a measurement alarm (insulation resistance,
overload or over temperature) is activated or deactivated. The data is written in the file
in the following order:
[TIME][Rer(kOhm)][Cer(uF)][Load(A)][Ttra(C)][Tenv(C)][Active PE Channels]
[TIME] = time stamp
[Rer(kOhm)] = insulation resistance (in kOhms)
If insulation resistance is “R>10M”, the measurement range has been exceeded.
This could be due to a disconnected wire, for example. Details of it can be found
in the event log.
If the value of insulation resistance is -1, a row has been added before the first
measurement was completed after the start-up.
[Cer(uF)] = capacitance (in micro farads)
If capacitance is “C<0.1”, the measurement range has been exceeded. This could
be due to a disconnected wire, for example. Details of it can be found in the
event log.
If the value of capacitance is -1, a row has been added before the first
measurement was completed after the start-up.
[Load(A)] = load (in amperes)
[Ttra(C)] = transformer temperature (in Centigrade)
[Tenv(C)] = device temperature (in Centigrade)
[Active PE Channels] = a list of all active (configured) PE channels
The format for one channel is PE
XX
CH
CC
NN
%,
in which
XX
= the PE address and
CC
= the channel number (1–6) and NN = channel resistance in relation to its
reference value in then table as a percentage.
If NN = -1.0, channel resistance has not been measured after the latest start-up.
All active and configured channels are listed one after the other (separated by
tabs).
After that, detailed information on the measurements that are not needed in normal use
is printed on the row. Therefore, they are not discussed here in greater detail.
All fields are separated with tabs, so the file is easy to handle in Excel.
Содержание SUPERINTEND IC-01
Страница 8: ...8 Copyright Muuntosähkö Oy Trafox Superintend IMD http www trafox fi Figure 1 System connection ...
Страница 21: ...Superintend IMD Copyright Muuntosähkö Oy Trafox 21 http www trafox fi ...
Страница 23: ...Superintend IMD Copyright Muuntosähkö Oy Trafox 23 http www trafox fi ...
Страница 28: ...28 Copyright Muuntosähkö Oy Trafox Superintend IMD http www trafox fi ...
Страница 35: ...Superintend IMD Copyright Muuntosähkö Oy Trafox 35 http www trafox fi ...
Страница 37: ...Superintend IMD Copyright Muuntosähkö Oy Trafox 37 http www trafox fi ...
Страница 70: ...70 Copyright Muuntosähkö Oy Trafox Superintend IMD http www trafox fi 36 3 mm 110 mm 62 mm ...