MODBUS/TCP REMOTE CONTROL
When IP settings suitable for a local area network are defined in the IM-01.MED unit, the
device can be connected to a LAN. The unit's Modbus/TCP slave server is now ready for
use. The unit’s Modbus/TCP register map is provided below. The Modbus functions to be
used are Read Holding Registers (0x03) and Write Multiple Registers (0x10).
Registe
r
R/
W
Name
Type
Unit
Description
1
R
Measured insulation resistance
uint16
kOh
m
The measurement result is provided as kOhms. The
register value 100 corresponds to insulation
resistance of 100,000 ohms. At the fastest, it updates
in seconds and at the slowest in hundreds of seconds,
depending on the measurement frequency used.
2
R
Measured capacitance
uint16
0.1
uF
The measurement result is provided as 0.1uF
intervals. The register value 5 corresponds to
capacitance of 0.5uF. It is updated at the same time
as the insulation resistance.
3
R
Measured load
uint16
%
The measurement result is provided as a percentage
of the announced nominal value. The register value
90 corresponds to the current value of 90% of the
announced nominal value. It is updated once per
second.
4
R
Measured temperature
uint16
°C
The measurement result is the transformer
temperature and it is provided as degrees. The
register value 50 corresponds to 50°C. It is updated
four times per second.
5
R/
W
Limit parameter of the
insulation resistance alarm
uint16
kOh
m
Read and written in kOhms. The register value 100
corresponds to 100,000 ohms. The minimum,
maximum and interval values are in channels 16, 17
and 18.
6
R/
W
The limit parameter of the
insulation resistance pre-alarm.
uint16
%
Read and written in percentages. The register value
150 corresponds to 150%. The minimum, maximum
and interval values are in channels 19, 20 and 21.
7
R/
W
Limit parameter of the load
alarm
uint16
%
Read and written in percentages. The register value
90 corresponds to 90%, The minimum, maximum
and interval values are in channels 22, 23 and 24.
8
R/
W
Limit parameter of the
temperature alarm
uint16
°C
Read and written in degrees. The register value 90
corresponds to 90°C, The minimum, maximum and
interval values are in channels 25, 26 and 27.
9
R/
W
Current transformer's nominal
value (primary current
corresponding to 5 A secondary
current), a device parameter
uint16
A
Read and written in amperes. The register value 40
corresponds to 40A. The minimum, maximum and
interval values are in channels 28, 29 and 30.
10
R/
W
Alarm delay, a device
parameter
uint16
s
Read and written in seconds. The register value 2
corresponds to 2 seconds. The minimum, maximum
and interval values are in channels 31, 32 and 33.
11
R
Password of the local user
interface
uint16
none
A three-digit password. Range 000…999. Default
value 123. When needed, this can be used to prevent
the parameters from being set through the
Modbus/TCP.
Содержание SUPERINTEND IC-01
Страница 8: ...8 Copyright Muuntosähkö Oy Trafox Superintend IMD http www trafox fi Figure 1 System connection ...
Страница 21: ...Superintend IMD Copyright Muuntosähkö Oy Trafox 21 http www trafox fi ...
Страница 23: ...Superintend IMD Copyright Muuntosähkö Oy Trafox 23 http www trafox fi ...
Страница 28: ...28 Copyright Muuntosähkö Oy Trafox Superintend IMD http www trafox fi ...
Страница 35: ...Superintend IMD Copyright Muuntosähkö Oy Trafox 35 http www trafox fi ...
Страница 37: ...Superintend IMD Copyright Muuntosähkö Oy Trafox 37 http www trafox fi ...
Страница 70: ...70 Copyright Muuntosähkö Oy Trafox Superintend IMD http www trafox fi 36 3 mm 110 mm 62 mm ...