5-17
Auxiliary Equipment Isolation Test, Cont.
Step Procedure,
Cont.
6.
Re-connect Battery Pack and measure Average Current. If
Average Current is less than or equal to equipment specification,
disconnect Battery Pack, reconnect next Auxiliary item, continue
to next step.
7.
Repeat Step 6 until all Auxiliary items have been tested and/or
equipment causing the power drain has been located.
If power drain has not been located, return to Power
Troublshooting Flow Chart (see
Figure 5–4).
TO BATTERY CABLE
TO CHARGER REGULATOR
RED DMM CONNECTOR
BLACK DMM CONNECTOR
Figure 5–6 Current Measurement Troubleshooting Cable
TFIO Module Isolation Test
If unit is configured to include TFIO Modules, this test will need to be performed if your units
Battery Pack output voltage is not remaining consistent and no errors were found during the
previous Auxiliary Equipment Isolation Test.
Instructions
Step
Procedure
1.
Disconnect Solar Panel Charger or AC Charger.
2.
Disconnect Battery Pack Cable from XRC-195 Board and
substitute known “Good Battery”, if not already done.
3.
Disconnect TFIO Module Cable from J18 I/O Expansion
Connector, Remote Communications equipment and auxiliary
equipment.
4.
Connect Current Measurement Troubleshooting Cable (Part No.
2017350-xxx see Figure 5–6), to known “Good Battery” and
connect to XRC-195 Board.
Continued on Next Page
Содержание XRC6490
Страница 1: ...2100802 001 AB TOTALFLOW XSeries Remote Controller User s Manual ...
Страница 6: ...iv B B Bl lla a an n nk k k P P Pa a ag g ge e e ...
Страница 10: ...viii B B Bl lla a an n nk k k P P Pa a ag g ge e e ...
Страница 19: ...1 5 Standard Enclosure Cont RC 6790 X Figure 1 2 Model XRC6790 Continued on Next Page ...
Страница 20: ...1 6 Standard Enclosure Cont 18 00 15 52 RC 6890 X 28 81 15 52 28 00 20 09 18 70 Figure 1 3 Model XRC6890 ...
Страница 24: ...1 10 XRC 195 Board Specifications Cont Figure 1 5 Complete View XRC 195 Board Continued on Next Page ...
Страница 41: ...1 27 Totalflow Input Output Modules Cont Figure 1 16 XRC6990 Inside View ...
Страница 42: ...1 28 B B Bl lla a an n nk k k P P Pa a ag g ge e e ...
Страница 56: ...2 14 AC Charging Unit Installation Cont Figure 2 12 DC Wiring Instructions Figure 2 13 AC Wiring Instructions ...
Страница 63: ...2 21 XRC Communication Jumper Settings and Field Wiring Cont Figure 2 19 Other Field Wiring I O Connections ...
Страница 64: ...2 22 B B Bl lla a an n nk k k P P Pa a ag g ge e e ...
Страница 86: ...4 12 Replacing XRC 195 Board Cont Figure 4 5 XRC Board Connections ...
Страница 88: ...4 14 B B Bl lla a an n nk k k P P Pa a ag g ge e e ...
Страница 112: ...5 24 12V Communication Supply Voltage Test Cont Figure 5 9 XRC 195 Communication Wiring ...
Страница 292: ...A 176 B B Bl lla a an n nk k k P P Pa a ag g ge e e ...
Страница 340: ...B 48 B B Bl lla a an n nk k k P P Pa a ag g ge e e ...
Страница 342: ...C 2 B B Bl lla a an n nk k k P P Pa a ag g ge e e ...