5-23
Transceiver Supply Voltage Test
Using wiring information and guidelines supplied by transceiver manufacturer, verify that
transceiver is receiving manufacturer’s suggested voltage. If unit is receiving sufficient
voltage, continue to the OEU Wiring Voltage Test.
If transceiver is not receiving sufficient voltage, investigate power supply
issues. These may involve wiring irregularities at either the AC
Charger/Power Supply system or XFC/XRC Board.
12V Communication Supply Voltage Test
Instructions
If Transceiver does not feature a SLEEP Mode and power is supplied
through an optional Relay, perform Step 1, Switched Power Supply
Voltage Test.
If Transceiver features a SLEEP Mode, or is continuously powered,
perform Step 2.
Step
Procedure
1.
If Transceiver does not feature a SLEEP Mode and receives
power through the XRC-195 Switched Power, activate Serial Port
1 or 2
Switched Power Out
(Pin 3) and, using a Digital Multimeter
(DMM) set to Volts DC, measure voltage at J6 between:
J6-2 (GND) and
J6-3 (SWVBAT)
If Voltage should be greater than 11.9VDC for this unit. If voltage
is equal to or less than 11.9, return to test sequence outlined in
the Power Troubleshooting Flowchart (see
Figure 5–4
).
2.
If Transceiver features a SLEEP Mode or is continuously
powered, using a Digital Multimeter (DMM) set to Volts DC,
measure voltage at J6 between:
J6-2 (GND) and
J6-1 (VBAT)
If Voltage should be greater than 11.9VDC for this unit. If voltage
is equal to or less than 11.9, return to test sequence outlined in
the Power Troubleshooting Flowchart (see
Figure 5–4
).
Continued on Next Page
Содержание XRC6490
Страница 1: ...2100802 001 AB TOTALFLOW XSeries Remote Controller User s Manual ...
Страница 6: ...iv B B Bl lla a an n nk k k P P Pa a ag g ge e e ...
Страница 10: ...viii B B Bl lla a an n nk k k P P Pa a ag g ge e e ...
Страница 19: ...1 5 Standard Enclosure Cont RC 6790 X Figure 1 2 Model XRC6790 Continued on Next Page ...
Страница 20: ...1 6 Standard Enclosure Cont 18 00 15 52 RC 6890 X 28 81 15 52 28 00 20 09 18 70 Figure 1 3 Model XRC6890 ...
Страница 24: ...1 10 XRC 195 Board Specifications Cont Figure 1 5 Complete View XRC 195 Board Continued on Next Page ...
Страница 41: ...1 27 Totalflow Input Output Modules Cont Figure 1 16 XRC6990 Inside View ...
Страница 42: ...1 28 B B Bl lla a an n nk k k P P Pa a ag g ge e e ...
Страница 56: ...2 14 AC Charging Unit Installation Cont Figure 2 12 DC Wiring Instructions Figure 2 13 AC Wiring Instructions ...
Страница 63: ...2 21 XRC Communication Jumper Settings and Field Wiring Cont Figure 2 19 Other Field Wiring I O Connections ...
Страница 64: ...2 22 B B Bl lla a an n nk k k P P Pa a ag g ge e e ...
Страница 86: ...4 12 Replacing XRC 195 Board Cont Figure 4 5 XRC Board Connections ...
Страница 88: ...4 14 B B Bl lla a an n nk k k P P Pa a ag g ge e e ...
Страница 112: ...5 24 12V Communication Supply Voltage Test Cont Figure 5 9 XRC 195 Communication Wiring ...
Страница 292: ...A 176 B B Bl lla a an n nk k k P P Pa a ag g ge e e ...
Страница 340: ...B 48 B B Bl lla a an n nk k k P P Pa a ag g ge e e ...
Страница 342: ...C 2 B B Bl lla a an n nk k k P P Pa a ag g ge e e ...