MAINTENANCE MANUAL
240
STE 85357
7.3.5
Replacement of Fuse (X8GN, X8GI Printed Board)
If the current exceeding the specified current has run through the I/O unit, the fuse in
the front of controller is blown out. If the
alarm saying “I/O Fuse Broken (8–273)” is
displayed, replace the fuse with a new one.
If the fuse of the output module has been blown out, examine and identify an fault
circuit, remedy the cause, then replace the fuse.
Fig. 7.11 Replacement of fuse (TS3000, TS3000E)
Table 7.3 Fuse (TS3000, TS3000E)
Type of fuse
Manufacturer
51NM030H
PICO
[Replacement procedures]
1)
Turn off the controller main power.
Fuse holder
Tighten