37
SC-F70
SC-F70
PID Operation Operating Instructions
3.2 Test Operation (LOC/MAN Mode)
This operation verifies the functions of the controller, the actuator (for
control valves, etc), and the sensor used in the system.
This section describes an example of the controller operation with the
Auto-tuning PID operation in which a general-purpose control valve is
used as the actuator (see Note 1).
In the heating, cooling PID operation, the control output value is fixed in
MAN mode, and the test operation described here cannot be run.
Therefore, set the PID constants for both heating and cooling (see Note
2) following "8. PID Constants Manual Tuning Method" (page 103),
then go to "3.3 Automatic Operation (LOC/AUT Mode)" (page 43).
Note 1: If you use other equipment for the actuator, consider the general-purpose
control valve as that equipment, and refer to this description. For details or
clarification, contact TLV.
Note 2: The heating, cooling PID operation has no Auto-tuning function, and PID
constants must be set manually.
®
®
®
®
®
Running the Test Operation
You can run the test operation by following two procedures:
1. Verifying the control valve actions in the MAN mode
2. Setting the PID constants by running auto-tuning