42
SC-F70
SC-F70
PID Operation Operating Instructions
4
Step
Action
PARA
AREA
ENT
A.SEL
DISP
MODE
PV
SC-F70
PARA
AREA
ENT
A.SEL
DISP
MODE
PV
SC-F70
∑
Start Auto-tuning
1
Press the Key several times until
"
" is displayed, blinking.
2
Press .
∑
Auto-tuning starts with the current Area
(preselected).
∑
The AT lamp starts blinking to show that Auto-
tuning is running.
∑
The AT lamp goes off when Auto-tuning ends.
∑
When Auto-tuning ends normally, the PID
constants are updated with optimal constant
values.
Note
PARA
AREA
ENT
A.SEL
DISP
MODE
PV
SC-F70
PARA
AREA
ENT
A.SEL
DISP
MODE
PV
SC-F70
Notes:
1. If you try to start Auto-tuning while the ramp operation is in process, Auto-tuning begins
after the end of ramp operation.
2. PID constants must be set into each Area you are going to use.
Each PID constant must match the target value of the Area.
3. The Auto-tuning operation sets the PID constants that will perform the best compensation
actions against possible external disturbance. If you want to improve the control
responsiveness, refer to "3.5 Compensation of Control Responsiveness" on page 51.
ENT
MODE
∑
To stop Auto-tuning immediately, do the following:
1
Press the Key. "
" will be
blinking.
2
Press .
∑
Auto-tuning stops and returns to Display mode.
∑
The AT lamp goes off.
∑
No update of PID constants takes place.
ENT
MODE