41
SC-F70
SC-F70
PID Operation Operating Instructions
1
Step
Action
∑
Choose an Area that you are going to set a target value
and PID constants for.
* Refer to " Key Operation Flow" on page 22.
∑
Enter the valve control target value into the selected
Area.
* Refer to " Key Operation Flow" on page 23.
∑
In the example on the right, 120.0 has been entered as a
target set value into Area number 1.
PARA
AREA
ENT
A.SEL
DISP
MODE
PV
SC-F70
PARA
AREA
ENT
A.SEL
DISP
MODE
PV
SC-F70
A.SEL
AREA
MODE
MODE
2
3
Set the mode to LOC with the Key.
* Refer to " Key Operation Flow" on page 25.
Notes:
1. In REM mode, Auto-tuning cannot be run.
2. Auto-tuning runs in either AUT or MAN.
When Auto-tuning ends, the controller resumes as follows.
Auto-tuning in AUT:
∑
Resumes in AUT mode.
∑
PID constants are updated for the
operation to resume.
Auto-tuning in MAN:
∑
Resumes in MAN mode.
∑
PID constants are updated.
∑
Operation resumes with the previous valve
control output value.