PID Operation Operating Instructions
There are two ways to use contact point Di1 on previous page, as defined
in the parameter PG06/DiGr item 1 (diS value): (refer to page 76)
diS value
0: MAN and AUT switching
1: LOC and REM switching
To start remote operation, set the mode to REM.
You can set REM mode either by setting the diS value to 1 and using the
contact for it, or you can set it using the control panel. Select the diS
value for the operation you plan to use.
Terminals 15 and 16 accept the analog input in either DC voltage or DC
current, as shown on previous page. The analog signal corresponds to the
target setting value.
®
®
®
®
®
Contact Operation
●
MAN and AUT Switching Plus Analog Input Contact Operation
(diS = 0)
Contact Action
Close to open
Open to close
Analog input signal
Terminal No.
No.12 - No.13(Di1)
No.15 - No.16
●
LOC and REM Switching Plus Analog Input Contact Operation
(diS = 1)
Contact Action
Close to open
Open to close
Analog input signal
Terminals No.
No.12 - No.13(Di1)
No.15 - No.16
Mode Switches To
LOC mode (about 2 seconds later)
REM mode (about 2 seconds later)
Mode Switches To
MAN mode (about 2 seconds later)
AUT mode (about 2 seconds later)