PID Operation Operating Instructions
6. PG07/AoGr (Transmission output)
Select the output range for
transmission output 2.
* This item is not displayed
when the cooling control
output is a current output in
the heating, cooling PID
operation.
Select the type for
transmission output 3.
* This item is not displayed
when the control output is a
current output.
Select the output range for
transmission output 3.
* This item is not displayed
when the control output is a
current output.
Range
Description
No.
Symbol
Name
Factory
setting
Lower
limit
Upper
limit
3
Lower
limit
Upper
limit
5
6
7
8
9
Lower limit for
transmission output 2
Upper limit for
transmission output 2
Type for transmission
output 3
Lower limit for
transmission output 3
Upper limit for
transmission output 3
When:
Ao2 = 0 or 2:
same as
measurement
range
(Note 2)
Ao2=1:
±
measurement
span
(Note 2)
Ao2=3 or 4:
0.0~100.0%
(2.AL < 2.AH)
0: Measured value
1: Deviation
2: Target setting
3: Control output
4: Cooling control
output
(Note 1)
When:
Ao3 = 0 or 2:
same as
measurement
range
( Note 2)
Ao3=1:
±
measurement
span
(Note 2)
Ao3=3 or 4:
0.0~100.0%
(3.AL <3.AH)
Notes: 1. The cooling control output can be selected in the heating, cooling PID
operation.
2. Use the same unit specified in the measurement input unit.
2.AL
2.AH
3.AL
Ao3
3.AH