PID Operation Operating Instructions
3.4 Area Switching Automatic Operation
(LOC/AUT Mode)
In the previous section, only one area (AG01) is used for the target control.
This section describes how to set up to 8 areas as needed. It also describes
how to select the area number for operation.
Operation Procedure
1
2
PARA
AREA
ENT
A.SEL
DISP
MODE
Target value
PV
SC-F70
Step
Action
ENT
PARA
AREA
ENT
A.SEL
DISP
MODE
Target value
PV
SC-F70
∑
Select LOC/MAN mode.
* If you need instruction, see page 25.
∑
Set up the areas.
* See page 23.
1
Press .
The panel looks like the example at right:
PV: Area group symbol (AG 1)
SV: Target set value of the area
Symbol: Symbol for the target setting (SV)
2
Change the setting value of each item as desired.
(See page 48 for the items you can set for each area)
a. Change the value by pressing or .
b. Register the value by pressing .
c. Go to the next item by pressing .
d. Repeat steps a to c for all the items.
Note: Press only when you do not need to
alter the value in these steps.
* You can use Auto-tuning to set PID constants
instead of manual setting in the Auto-tuning PID
operation. Refer to "Procedure-2 Setting the PID
Constants with Auto-tuning" on page 40.
3
Press to move to Area No. 2.
Area Group 2 (AG 2) will appear as shown at right.
Set all items in the group as described in step
.
4
Repeat steps
1
to 3 above to set as many AREA groups as you want to use.
* Each AREA must have its optimal PID constants.
AREA
<
ENT
ENT
<
AREA