61
SC-F70
SC-F70
PID Operation Operating Instructions
®
®
®
®
®
Remote Area Switching Operation
The next procedure describes how to run the controller using remote
area switching.
1
2
3
Step
Action
MODE
ENT
∑
Set the diS parameter of the PG06. See page 76.
∑
Set the external contacts to a new area number for operation.
Note: Do not change the mode to REM/AUT before a new area number
setting is completed. Otherwise, an unexpected area number will be
selected, or a selection error will occur.
∑
Set the mode to REM.
Do the following on the operation panel (diS = 0 and 2):
LOC
Æ
REM switching (Operation panel)
1 Press twice.
* LOC and REM (blinking) appear on the Symbol and SV display,
respectively.
2 Press .
* The REM lamp of the status indicator turns on, and the panel changes to
display state.
or
Do the following if you use the external contact (on back panel) (diS = 1):
LOC
Æ
REM switching (External contact)
1 If Dil contact point is open, close it; if closed, open and close it.
∑
Set the mode to AUT.
Do the following on the operation panel (diS = 1 and 2):
MAN
Æ
AUT switching (Operation panel)
1 Press once.
* MAN and AUT (blinking) appear on the Symbol and SV display,
respectively.
2 Press .
* The AUT lamp of the status indicator turns on, and the panel changes to
the display state.
or
Do the following when you use the external contact (on back panel) (diS = 0):
MAN
Æ
AUT switching (External contact)
1 If Dil contact point is open, close it; if closed, open and close it.
∑
Once this procedure is completed, the new area number set by the external
contacts is used by the controller.
4
MODE
ENT
5