PID Operation Operating Instructions
5. DC current input
Input values:
0-20 mA, 4-20 mA
Input impedance: Approximately 250
W
(2) Measurement accuracy:
±
(0.1%F.S. + 1 digit)
(3) Sampling period:
0.25 second
(4) Measurement Input Bias:
±
(5% of measurement span)
(5) PV Digital Filter:
Primary delay filter 0-100 seconds
(variable)
Note: when set to 0, PV Digital
Filter is OFF.
9.3 Settings
(1) Setting range (SV):
Same as measurement range
(2) Setting resolution:
Depending on measurement input
range
(3) Setting limiters (upper/lower):
Arbitrary value within measurement
input range
(4) Soft start time:
0.00 to 99.59
Note: Unit selectable (hour.minute
or minute.second)
(5) Setting change rate limiter:
0.0 to measurement span %/minute
Note: When set to 0.0, the setting
change rate limiter is OFF.
(6) AREA function
Number of AREAs:
8
AREA switching method:
* Using keys on front panel
* Through external contacts when
model is equipped with area switching
external input feature
* Through communications when
model is equipped with
communication feature