PID Operation Operating Instructions
1. PG02/PVGr (measurement input)
Range
No.
Symbol
Name
Factory
setting
Depends
on order
specifi-
cations.
Depends
on order
specifi-
cations.
0
0.00
0
0.00
Depends
on order
specifi-
cations.
0 to 701
-199.9 to 999.9
(See Note1)
1. PVL < PVH
2. For decimal
position, see
item No. 6.
0 to 100 sec.
±
5 % of
measurement
span [Measure-
ment unit]
(See Note 2)
0: Not
required
1: Required
0.00 ~ 25.00%
0 - 3
To set this value, see the table
of Measurement Input Types
and Ranges shown on the next
page.
These values are used to set a
range for the sensor used.
* When the PVI range is set
between 0 to 511, these
parameters do not appear.
Applies a first-order lag to
reduce noise from
measurement input.
Applies bias to measurement
input for sensor accuracy
correction.
Specifies if an extraction
function of the square root is
required.
* This parameter is displayed
only when the measurement
type PVI is set to 600-701.
Cuts low values and
measurements that may
amplify the result of the
extraction of the square root.
* This parameter is displayed
only when PVr=1.
Designates the decimal
position for measurement
input by the number of digits
after the point. (See Note 3)
Description
1
Measurement input
type
Lower limit of
measurement input
range
Upper limit of
measurement input
range
Measurement input
filter
Measurement input
bias
Extraction of the
square root of
measurement input
Low-cut of
measurement input
Decimal position
PVH
PVL
PVI
PVF
4
3
2
5
PVb
PVr
6
PVc
dp
8