106
SC-F70
SC-F70
PID Operation Operating Instructions
9. Specifications
This chapter provides product specifications for pressure control.
9.1 Display Functions
(1) Measured value (PV) display:
4-digit 7-segment LED (orange)
(2) Set value (SV) display:
4-digit 7-segment LED (orange)
(3) Symbol display:
3-digit 7-segment LED (orange)
(4) Operation LED:
1 SFT (Soft start control):
surface-emitting LED (green)
2 AUT (Auto mode):
surface-emitting LED (green)
3 REM (Remote mode):
surface-emitting LED (green)
4 AT (Auto-tuning):
surface-emitting LED (orange)
5 AL1-AL4 (Alarms):
surface-emitting LED (red)
6 FAIL (Fail status):
surface-emitting LED (red)
7 UP (Up deviation):
surface-emitting LED (orange)
8 DOWN (Down deviation): surface-emitting LED (green)
9.2 Measurement Input
(1) Types
1. Thermocouple input
Input values:
K, J, E, T, U, L
Signal source resistance:
Approximately 0.2
m
V/
W
Input impedance:
1M
W
min.
2. RTD input
Input values:
Pt100, JPt100
Sensor current:
Approximately 0.25mA
Input line resistance range:
10
W
max.
3. DC voltage (LOW) input
Input values:
0-10 mV, 0-100 mV, 0-1 V
Input impedance:
Approximately 1 M
W
Input voltage range:
Within
±
4 V
4. DC voltage (HIGH) input
Input values:
0-5 V, 1-5 V, 0-10 V
Input impedance:
Approximately 1 M
W
Input voltage range:
Within
±
12 V