Fan Coil Actuator FCA 2
Updated: Feb-16 (subject to changes) Page
48
of
89
3.4.13
Parameter page Operating mode and operation (internal
controller)
Table 32
Designation
Values
Meaning
Operating mode after reset Frost/heat protection
Temperature reduction at night
Standby
Comfort
Operating mode after start-up
or reprogramming
Transmission of current
operating mode every
do not send cyclically
3 min, 5 min, 10 min
15 min, 20 min, 30 min
60 min
Cyclical transmission time of
operating mode (object 24)
Objects for operating
mode selection
new: operating mode, presence,
window status
FCA 2 can switch the
operating mode depending on
the window and presence
contacts.
old: Comfort, night, frost (not
recommended)
Traditional setting without
window and presence status.
Type of presence detector
The presence sensor activates
the comfort operating mode
Presence detector
Comfort operating mode as
long as the presence object is
set.
Presence buttons
If the operating mode object
(Object 3) is called up again
after setting the presence
object, the new operating
mode will be accepted and the
presence object reset.
If the presence object is set
during night/frost mode, it is
reset after the configured
comfort extension finishes
(see below).
The presence object is not
reported back on the bus.