Fan Coil Actuator FCA 2
Updated: Feb-16 (subject to changes) Page
35
of
89
3.4.4 Parameter page Cooling valve
Table 23
Designation
Values
Meaning
Time for closing the valve
0 min, 1 min, 2 min,
3 min, 4 min, 5 min,
6 min, 7 min, 8 min,
9 min, 10 min, 15 min,
20 min, 30 min
Adjustment to the used
actuator.
Repositioning at change by
0 %,
The valve will be repositioned
at each change of the
actuating value.
1 %, 2 %, 3 %,
4 %, 5 %, 6 %, 7 %
8 %, 9 %, 10 %, 11 %
12 %, 13 %, 14 %, 15 %
The valve will only be
repositioned if the actuating
value has changed by more
than the set value, compared
to the last positioning. This
enables frequent, small
positioning increments to be
suppressed.
Open from actuating
value*
0.4 %,
Valve is opened even with
minimum actuating value.
5 %, 10 %
15 %, 20 %, 25 %
30 %, 35 %, 40 %
Valve is only opened once the
actuating value has reached
the set value.
This setting prevents possible
whistling when valve is open.
Minimum valve setting*
0 %, 5 %, 10 %, 15 %,
20 %, 25 %, 30 %, 35 %,
40 %, 45 %, 50 %
Minimum permissible valve
setting with actuating value <
> 0%..
Maximum valve setting
from actuating value*
0.4 %, 10 %, 20 %, 30 %
40 %, 50 %, 60 %, 70 %
80 %, 90 %, 100 %
Actuating value from which
the valve accepts maximum
valve setting.
Maximum valve setting*
55 %, 60 %, 65 %, 70 %
75 %, 80 %, 85 %, 90 %,
95 %,100 %
Maximum permissible valve
setting
Transmission of cooling
status every
do not send cyclically
3 min, 5 min
10 min, 15 min
20 min, 30 min
60 min
Cyclical transmission time for
cooling status (object 2)
* Setting of valve characteristic, see appendix: Setting valve characteristic.