![Theben FCA 2 Скачать руководство пользователя страница 13](http://html.mh-extra.com/html/theben/fca-2/fca-2_manual_1101137013.webp)
Fan Coil Actuator FCA 2
Updated: Feb-16 (subject to changes) Page
13
of
89
3.3.2 Description of objects
•
Object 0 "Actuating value for fan" / "Actuating value heating/cooling" transmit or
receive.
The function of the object is connected with the parameters "
Supported function
" and
"
Type of controller used
" on the "
General
" parameter page.
Table 4.
Supported
function
Kind of controller used
and
Function of object
Installation type
internal controller
external controller
Heating
Transmits the current
actuating value of heating
valve
Receives the actuating
value for the heating valve
4-pipe system or
heating only
system
Cooling
Transmits the current
actuating value of cooling
valve
Receives the actuating
value for the cooling valve
cooling only
system
Heating and
cooling
Transmits the current
actuating value of the
common heating and
cooling valve
Receives the actuating
value for the common
heating and cooling valve
2-pipe system
Fan
receives the actuating value for fan control
Ventilation