Fan Coil Actuator FCA 2
Updated: Feb-16 (subject to changes) Page
51
of
89
3.4.15
Parameter page Actuating value loss
This parameter page is only visible if an external controller is used and if this function has been
selected on the
General
parameter page (parameter:
Should the actuating value be monitored
).
Table 34
Designation
Values
Meaning
Monitoring time for
actuating value
30 min
60 min
If no actuating value is
received within the
configured time, the substitute
activating value applies.
Substitute actuating value
in case of actuating value
loss
(emergency program)
0 %, 10 %, 20 %
30 %, 40 %, 50 %, 60 %,
70 %, 80 %, 90 %, 100 %
Actuating value for the
emergency program as long
as no new actuating value is
received by the room
thermostat
Report actuating value
loss
(1 = actuating value loss)
only if object value = 1
Object 20 only transmits at
actuating value loss.
always cyclically
Object 20 always transmits
the status of the actuating
value.
0 = OK
1 = actuating value loss
Report cyclically
every 3 min, every 5 min
every 10 min, every 15 min
every 20 min, every 30 min
every 45 min, every 60 min
Cycle time for actuating value
status.