Fan Coil Actuator FCA 2
Updated: Feb-16 (subject to changes) Page
24
of
89
•
Object 31 "Change filter "
This object is available if the "
Should a filter change be reported
" parameter is set to "
yes
".
This object has 2 functions:
1.
As sending object:
Sends a 1 once the configured operating time of the fan has been reached.
See "
Report filter change after fan operation (1..127 weeks)
" on the "
Filter monitoring
"
parameter page.
2.
As receiving object:
Reset for the
Filter change
status and the fan operating our counter (object 30).
0 = Reset.
•
Object 32 "Test mode"
Sends a telegram if the device is set to test mode
(1 = Test mode).
See also: Test mode in the Start-up chapter.