Parameter page Filter monitoring
This parameter page is only visible if this function has been selected on the
General
parameter
page (parameter:
Should a filter change be reported
).
Table 33
Designation
Values
Meaning
Report filter change after
fan operation
(1..127 weeks)
manual input: 1..127
(Standard 12)
interval between 2 filter
changes in weeks.
Cyclical transmission of
filter change
only at filter change
Object 31 only sends when
filter change is required:
1 = Change filter
always cyclically
Object 31 sends the filter
status cyclically:
0 = Filter OK
1 = Change filter
Transmit fan duty time*
(in hours)
send never
(reading is possible)
The fan duty time is counted
to the second internally, but
not transmitted.
The meter reading can be read
from object 30.
only at change
The meter reading is
transmitted every time the fan
duty time increases by 1 hour.
cyclically and at change
The meter reading is
transmitted at regular
intervals and at changes.
Send cyclically
every 3 min, every 5 min
every 10 min, every 15 min
every 20 min, every 30 min
every 45 min, every 60 min
Cyclical transmission time for
meter reading.
* To reset the filter status and the meter reading, see object 31.