Fan Coil Actuator FCA 2
Updated: Feb-16 (subject to changes) Page
11
of
89
Continuation:
No.
Function
Object name
Type
C R W T
8
Fan stage in forced
operation
Fan control with % value
1 byte
5,001
C R W -
Fan stage in forced
operation
Fan control via level
1 byte
5,010
C R W -
9
Limitation of fan stage in %
0=Fan OFF 1..100%=max.
1 byte
5,001
C R W -
Limitation of fan stage in %
0=Fan OFF
1..100%=max.stage
1 byte
5,001
C R W -
Limitation of fan stage (1-2-
3)
0=Fan OFF
1-3=max.stage
1 byte
5,010
C R W -
10
Fan off
Report
1 bit
1,001
C R - T
11
Fan stage 1
Report
1 bit
1,001
C R - T
12
Fan stage 2
Report
1 bit
1,001
C R - T
13
Fan stage 3
Report
1 bit
1,001
C R - T
14
Status of window contact at
E1
Report
1 bit
1,019
C R - T
Actual value at E1
Report
2 byte
9,001
C R - T
15
Fan auto/forced mode
Receive: Auto = 1, Forced =
0
1 bit
1,001
C R W -
Fan Forced/Auto
Receive: Forced = 1, Auto =
0
16
Status of condensation
monitoring
Input
1 bit
1,001
C R W -
Status of condensation
monitoring
Report
C R - T
Status of window contact at
E2
Report
1 bit
1,019
C R - T
17
Dew point alarm
Input
1 bit
1,001
C R W -
18
Outdoor temperature
Input
2 byte
9,001
C R W -
19
Adjust setpoint
Delta in K
2 byte
9,002
C R - T
Adjust setpoint
Value in °C
2 byte
9,001
C R - T
20
Actuating value loss
1 = Actuating value loss
1 bit
1,001
C R - T
Sensor failure
Sensor failure