Fan Coil Actuator FCA 2
Updated: Feb-16 (subject to changes) Page
39
of
89
3.4.8 Parameter page E2
This page is only available if the
Supported function
parameter is set to
Heating
(General
parameter page).
Table 27
Designation
Values
Meaning
Function of E2
Contact closed = window closed
Contact open = window closed
Type of connected contact
(opening contact or NO
contact)
Transmission of E2 status
every
do not send cyclically
3 min, 5 min, 10 min, 15 min,
20 min, 30 min,
60 min
Cyclical transmission time for
input E2
3.4.9 Parameter page Condensation monitoring
Table 28
Designation
Values
Meaning
Source for drip tray
monitoring
E2
Condensate is reported to E2
via a contact
Object 16
Condensate is reported to
object 16 via the bus.
Direction of action of E2
Contact closed = Condensate
Contact open = Condensate
Type of connected condensate
report contact or condensate
telegram.
Behaviour in case of
condensate
Cooling off and fan off
Cooling off and fan stage 1
Cooling off and max. fan stage
Only report
Reaction to condensate alarm
Transmission of
condensate status every
do not send cyclically
3 min, 5 min, 10 min, 15 min
20 min, 30 min,
60 min
Cyclical transmission time for
condensate.