![Theben FCA 2 Скачать руководство пользователя страница 70](http://html.mh-extra.com/html/theben/fca-2/fca-2_manual_1101137070.webp)
Fan Coil Actuator FCA 2
Updated: Feb-16 (subject to changes) Page
70
of
89
6.2 Setting the valve characteristic
The parameters on the
heating valve
and
cooling valve
pages allow an exact adjustment to the
available valve type or allow the slight adjustment of the control.
Example for a valve that starts to open from a position of 10 % and is already completely open at
80 %.
Figure 9
Table 59
Description
Value
X Actuating value from the controller
0 .. 100 %
Y Resulting valve setting
0 .. 100 %
A Parameter: Minimum valve setting
20 %
B Parameter: Maximum valve setting
80 %
C Parameter: Open from actuating value
10 %
D Parameter: Maximum valve setting from actuating
value
90 %