Fan Coil Actuator FCA 2
Updated: Feb-16 (subject to changes) Page
18
of
89
•
Object 11 "Fan stage 1"
Only available if
fan controller
=
standard
.
Report object for the fan status.
Sends a 1 if the fan is switched to stage 1.
•
Object 12 "Fan stage 2"
Only available if
fan controller
=
standard
.
Report object for the fan status.
Sends a 1 if the fan is switched to stage 2.
•
Object 13 "Fan stage 3"
Only available if
fan controller
=
standard
.
Report object for the fan status.
Sends a 1 if the fan is switched to stage 3.
•
Object 14 "Actual value at E1", "Window contact status at E1"
The object function depends on the "
Function of E1
" parameter on the "
E1
" parameter page.
Table 10
Parameters
"Function of E1"
Meaning
E1 = Window contact
Sends the current status of the window contact to the bus.
→ Only available when using an external controller.
E1 = Actual value
sensor
Sends the currently measured room temperature to the bus.
→ Fixed setting when using an internal controller.
•
Object 15 "Fan forced/ auto", "fan auto/forced"
This object is used to activate or leave the forced operation of the fan.
The desired fan stage or speed for forced operation is set by Object 8.
The direction of action of the forced object is adjustable on the
General
parameter page.
The forced operation of the fan has no effect on valve control.