Fan Coil Actuator FCA 2
Updated: Feb-16 (subject to changes) Page
78
of
89
6.7.2 Old operating modes
If Old... is selected in the "Determination of operating mode" parameter on the "Operating mode"
parameter page, the current operating mode can be defined as follows:
Table 63
Night
Object 21
Comfort
Object 22
Frost/heat protection object 23 current operating mode
Object 24
any
any
1
Frost/heat protection
any
1
0
Comfort
Standby
0
0
Standby
Night
0
0
Night
Typical application:
In the mornings, "standby" mode, and in the evenings "night" mode are
activated by a time switch via object 21.
In holiday periods, frost/heat protection is selected via another channel of the time switch via
Object 23.
Object 22 (comfort) is connected to a presence detector. If presence is detected, FCA 2 switches
to comfort operating mode (see table).
Object 23 is linked with a window contact: As soon as a window is opened, FCA 2 switches to
frost protection mode.
Standby
0 Night
object
0 Comfort object
Night
1
0 Frost
object
Comfort
1
Current
Operating
mode
Frost
protection
1
Figure 13
The old method has 2 disadvantages over the new method:
1.
To switch from Comfort to Night operating mode, 2 telegrams (2 time switch channels if
necessary) are required: Object 4 must be set to "0" and Object 3 to "1".
2.
If the window is opened and then closed again during periods when "Frost/heat
protection" is selected via the time switch, the "Frost/heat protection" mode is cleared.