![Theben FCA 2 Скачать руководство пользователя страница 27](http://html.mh-extra.com/html/theben/fca-2/fca-2_manual_1101137027.webp)
Fan Coil Actuator FCA 2
Updated: Feb-16 (subject to changes) Page
27
of
89
3.4.2 Parameter page Fan
3.4.2.1
Fan controller = standard (1-3 stages)
IMPORTANT:
The difference between the 2 switch-on thresholds must be
at least 15 %
.
Table 20
Designation
Values
Meaning
Fan controller
standard (1-3 stages)
A standard fan with up to 3
stages is used.
(Connectors
S1
,
S2
,
S3
and
N
).
0-10 V
A fan with 0-10 V controller
is used
(Connectors
F+
and
GND
).
Number of fan stages
1 stage
2 stages
3 stages
Available number of fan
stages.
Switch-on threshold for
fan stage 1
0.4 %, 5 %, 10 %, 15 %,
20 %, 25 %, 30 %
35 %, 40 %
Determines from which
actuating value stage 1 should
switch on.
Switch-on threshold for
fan stage 2
0 %, 10 %, 20 %
30 %, 40 %, 50 %
60 %, 70 %, 80 %
90 %, 100 %
Determines at which actuating
value stage 1 should change
to stage 2.
Switch-on threshold for
fan stage 3
0 %, 10 %, 20 %
30 %, 40 %, 50 %
60 %, 70 %, 80 %
90 %, 100 %
Determines at which actuating
value stage 2 should change
to stage 3.