COMMUNICATION MANUAL
GXE600 SERIES
TDKLambda
<Page>
69/79
#
17
Re gist e r Nam e
Clear Alarm History
Data Type
Register Function
Starting Address
Qty
Non-volatile
Holding
Protection operation history erase
1
No
1) Register Details
This register is used to request clearance of alarm history.
Normally, the contents of the alarm history register are automatically erased when switching from Remote Off to Remote On,
but by writing this register, it is also possible to erase the history.
・Use Case 1
By polling the operations of read "Alarm history register" and write "Alarm history erase
register", it is possible to acquire only new protection factors that occurred during polling.
・Use Case 2
It is a specification that the alarm history remains even when the protection function with automatic recovery setting operates.
When the current alarm history is unnecessary, this function can clear the alarm history without stopping the power supply.
・Register setting value
Data Type
Clear
Ignore
Unit
16 bit integer
1
0
-
* If an unspecified value is written, only the lowest bit is accepted as a valid value.
2) Register Read
This register is write-only, and an exception response (exception code: 0x03) is returned for a read query.
3) Register Write
R eques t PD U
Write Holding.
Field
Byte
Value
Function code
1
0x 06
Starting Address
2
115 (0x0073)
Registers value
2
writing data.
R es pons e PD U
Write Holding.
Field
Byte
Value
Function code
1
0x 06
Starting Address
2
115 (0x0073)
Register value
2
echo query data.
E rror PD U
Write Holding.
Field
Byte
Value
Function code
1
0x 86
Exception code
1
0x02 / 0x03 / 0x04
115
(0x0073)