COMMUNICATION MANUAL
GXE600 SERIES
TDKLambda
<Page>
31/79
#
7
Re gist e r Nam e
Model Name of Product
Data Type
Register Function
Starting Address
Qty
Non-volatile
Input
Strings of device model name. [ASCII]
15
Yes
1) Register Details
This register is the product model name registered in GXE, and it is written in ASCII.
Handle register data as character array of 8 bit data x 30.
Valid as "Product model name" is data from the beginning to the terminating character [NULL 0x00].
Product model name is retained even when input is cut off.
Example : Model name is "GXE600-24".
Request PDU
Response PDU
9 bytes of D 0 to D 8 are valid as character string data in the data bytes.
2) Register Read
R eques t PD U
Read Inputs.
Field
Byte
Value
Function code
1
0x 04
Starting Address
2
500 (0x01F4)
Quantity of Registers
2
15 (0x000F)
R es pons e PD U
Read Inputs.
Field
Byte
Value
Function code
1
0x 04
Byte count
1
30 (2 x 15)
Registers value
30
Reading data.
E rror PD U
Read Inputs.
Field
Byte
Value
Function code
1
0x 84
Exception code
1
0x02/0x04
500
(0x01F4)
'G'
'X'
'E'
'6'
'0'
'0'
'-'
FC
Bytes
D0
D1
D2
D3
D4
D5
D6
0x04 0x1E
0x47
0x58
0x45
0x36
0x30
0x30 0x2D
D7
D8
D9
D28
D29
0x32
0x34
0x00
0x00
0x00
'2'
'4'
FC
0x04 0x01 0xF4 0x00 0x0F
Start Address
Quantity