COMMUNICATION MANUAL
GXE600 SERIES
TDKLambda
<Page>
55/79
#
10
Re gist e r Nam e
Rising Time of Output Current
Data Type
Register Function
Starting Address
Qty
Non-volatile
Holding
Current slew rate at output start
1
Yes
1) Register Details
This is the configuration register for current slew rate when GXE starts outputting.
The CC slew rate (di / dt) is specified as the time required for the CC reference value to change from 0% to 100%.
Configuration data is retained even when input is cut off.
・Register value
Data Type
Max
Min
Factory setting
Unit
16 bit integer
10000
20
20
ms
*An exception response (Exception code: 0x03) is returned when writing values outside the range.
This function is the setting of the reference value, and it does not necessarily operate as set up.
Depending on the load impedance, the output current may not follow the CC reference.
CC reference value is changed during steady state, the slew rate setting of the [# 12 Rising Time of Output current]
register is applied, not this register.
This register is set by time, but it is used to determine the slew rate.
Actual changing time is equivalent to ΔCC reference value / rated value.
Example) CC reference value : 0.85 [Q10] , Register setting value : 10000 [ms]
Actual changing time = Register setting value x CC reference value / Rated value
= 10000 x 0.85 / 1.0 = 8500 [ms]
108
(0x006C)
設定値
T
0
dt
最小
最大
t [msec]
d i
CC [%]
100
Setting value
Min.
Max.
t [ms]