COMMUNICATION MANUAL
GXE600 SERIES
TDKLambda
<Page>
65/79
#
15
Re gist e r Nam e
PF Count
Data Type
Register Function
Starting Address
Qty
Non-volatile
Holding
PF signal output confirmation time limit setting
1
Yes
1) Register Details
This is the configuration register for PF (Power Fail) signal output confirmation time (delay time).
The setting value is specified by integer data [ms].
When the output is below the PF detection threshold for a time longer than the set time, the PF signal is output
When the output returns to the PF detection threshold or higher within the set time, the PF signal is not output.
The PF signal detection level is set in the PF threshold register.
The PF signal detection target is selected by the PF mode setting register.
Configuration data is retained even when input is cut off.
・Register setting value
Data Type
Max
Min
Factory setting
16 bit integer
100
0
0
*An exception response (Exception code: 0x03) is returned when writing values outside the range.
Unit
ms
113
(0x0071)
確認時限
[0
~
100 msec]
0
t
Vo / Io
PF
閾値
PF
信号
PF detection threshold
PF signal
Check time limit [0 ~ 100 ms]