COMMUNICATION MANUAL
GXE600 SERIES
TDKLambda
<Page>
57/79
#
11
Re gist e r Nam e
Changing Time of OutputVoltage at steady state
Data Type
Register Function
Starting Address
Qty
Non-volatile
Holding
Voltage slew rate at steady state setting
1
Yes
1) Register Details
This is the configuration register for slew rate when PV reference value is changed during steady state.
The PV slew rate (dv / dt) is specified as the time required for the PV reference value to change from 0% to 100%.
Please do one of the following methods to validate the setting value.
・ Re-input
・ From Remote Off to Remote On
Configuration data is retained even when input is cut off.
・Register setting value
Data Type
Max
Min
Factory setting
16 bit integer
10000
20
20
*An exception response (Exception code: 0x03) is returned when writing values outside the range.
This function is the setting of the reference value, and it does not necessarily operate as set up.
Depending on the load impedance, the output current may not follow the PV reference.
To change the PV value at startup, the slew rate setting of the [# 11 PV reference rise time] register is applied, not this
register.
The value set here is the time required for a change of 0% ⇒ 100%
Actual changing time is equivalent to ΔPV reference value / rated value.
Example) PV reference value : 0.5 ⇒ 1.0 [Q10]、Register setting value : 1000 [ms]
Actual changing time = Register setting value x ΔPV reference value / Rated value
= 1000 x (1.0 - 0.5) / 1.0 = 500 [ms]
Unit
ms
109
(0x006D)
設定値
T
実際の遷移時間
0
dV
dt
t [msec]
PV [%]
100
50
dv
Actual changing time
Setting value
t [ms]